Rheem RRPL-B Installation Instructions Manual page 46

Table of Contents

Advertisement

GENER L D T - RRNL- MODELS
NOMIN L SIZES 2-5 TONS [7-15.8 kW]
Model RRNL- Series
1
Cooling Performance
Gross Cooling Capacity Btu [kW]
2
EER/SEER
Nominal CFM/AHRI Rated CFM [L/s]
AHRI Net Cooling Capacity Btu [kW]
Net Sensible Capacity Btu [kW]
Net Latent Capacity Btu [kW]
Net System Power kW
4
Heating Performance (Gas)
Heating Input Btu [kW]
Heating Output Btu [kW]
Temperature Rise Range ºF [ºC]
AFUE %
Steady State Efficiency (%)
No. Burners
No. Stages
Gas Connection Pipe Size in. [mm]
Compressor
No./Type
5
Outdoor Sound Rating (dB)
Outdoor Coil - Fin Type
Tube Type
Tube Size in. [mm] OD
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Indoor Coil - Fin Type
Tube Type
Tube Size in. [mm]
Face Area sq. ft. [sq. m]
Rows / FPI [FPcm]
Refrigerant Control
Drain Connection No./Size in. [mm]
Outdoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
CFM [L/s]
No. Motors/HP
Motor RPM
Indoor Fan - Type
No. Used/Diameter in. [mm]
Drive Type/No. Speeds
No. Motors
Motor HP
Motor RPM
Motor Frame Size
Filter - Type
Furnished
(NO.) Size Recommended in. [mm x mm x mm]
Refrigerant Charge Oz. [g]
Weights
Net Weight lbs. [kg]
Ship Weight lbs. [kg]
NOTES:
1. Cooling Performance is rated at 95°F ambient, 80°F entering dry bulb, 67°F entering wet bulb. Gross capacity does not include the effect of fan motor heat. ARI capacity is
net and includes the effect of fan motor heat. Units are suitable for operation to ±20% of nominal cfm. Units are certified in accordance with the Unitary Air Conditioner
Equipment certification program, which is based on ARI Standard 210/240 or 360.
2. EER and/or SEER are rated at ARI conditions and in accordance with DOE test procedures.
3. Heating Performance limit ettings and rating data were established and approved under laboratory test conditions using American National Standard Institute standards.
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings should be reduced at the rate of 4% for each 1000 feet above sea level.
4. AFUE is rated in accordance with DOE test procedures.
5. Outdoor Sound Rating shown is tested in accordance with ARI Standard 270.
46
B036CK06
B036CK08
37,000 [10.84]
37,000 [10.84]
11.3/13
11.3/13
1200/1200 [566/566]
1200/1200 [566/566]
35,600 [10.43]
35,600 [10.43]
26,390 [7.73]
26,390 [7.73]
9,210 [2.7]
9,210 [2.7]
3.15
3.15
60,000 [17.58]
80,000 [23.44]
48,600 [14.24]
64,800 [18.99]
30-60 [16.7-33.3]
40-70 [22.2-38.9]
80
80
81
81
3
4
1
1
0.5 [12.7]
0.5 [12.7]
1/Scroll
1/Scroll
76
76
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
14.8 [1.37]
14.8 [1.37]
1 / 22 [9]
1 / 22 [9]
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
5.54 [0.51]
5.54 [0.51]
2 / 15 [6]
2 / 15 [6]
TX Valves
TX Valves
1/0.75 [19.05]
1/0.75 [19.05]
Propeller
Propeller
1/22 [558.8]
1/22 [558.8]
Direct/1
Direct/1
2700 [1274]
2700 [1274]
1 at 1/3 HP
1 at 1/3 HP
1075
1075
FC Centrifugal
FC Centrifugal
1/10x9 [254x229]
1/10x9 [254x229]
Direct/3
Direct/3
1
1
1/2
1/2
1075
1075
48
48
Field Supplied
Field Supplied
No
No
(1)1x24x24 [25x610x610]
(1)1x24x24 [25x610x610]
92.8 [2631]
92.8 [2631]
417 [189]
422 [191]
457 [207]
462 [210]
B036CK10
B036DK06
Continued ->
37,000 [10.84]
37,000 [10.84]
11.3/13
11.3/13
1200/1200 [566/566]
1200/1200 [566/566]
35,600 [10.43]
35,600 [10.43]
26,390 [7.73]
26,390 [7.73]
9,210 [2.7]
9,210 [2.7]
3.15
3.15
100,000 [29.3]
60,000 [17.58]
81,000 [23.73]
48,600 [14.24]
45-85 [25-47.2]
30-60 [16.7-33.3]
80
80
81
81
5
3
1
1
0.5 [12.7]
0.5 [12.7]
1/Scroll
1/Scroll
76
76
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
14.8 [1.37]
14.8 [1.37]
1 / 22 [9]
1 / 22 [9]
Louvered
Louvered
Rifled
Rifled
0.375 [9.5]
0.375 [9.5]
5.54 [0.51]
5.54 [0.51]
2 / 15 [6]
2 / 15 [6]
TX Valves
TX Valves
1/0.75 [19.05]
1/0.75 [19.05]
Propeller
Propeller
1/22 [558.8]
1/22 [558.8]
Direct/1
Direct/1
2700 [1274]
2700 [1274]
1 at 1/3 HP
1 at 1/3 HP
1075
1075
FC Centrifugal
FC Centrifugal
1/10x9 [254x229]
1/10x9 [254x229]
Direct/3
Direct/2
1
1
1/2
1/2
1075
1075
48
48
Field Supplied
Field Supplied
No
No
(1)1x24x24 [25x610x610]
(1)1x24x24 [25x610x610]
92.8 [2631]
92.8 [2631]
426 [193]
417 [189]
466 [211]
457 [207]

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rrnl-cRrnl-bRrrl-c