Carrier 58MVP Troubleshooting Manual page 17

Variable-speed 2-stage electronic condensing furnace

Advertisement

Fault Code 21
INVALID MODEL SELECTION—Personality connector PL5 is either not connected or jumpered wrong.
STEP
1.
Turn power off and remove blower access panel.
Is personality connector PL5 properly wired per furnace model size chart on
2.
wiring diagram?
3.
Replace or rewire personality connector.
Go to page number indicated in Index for CLEANUP AND START-UP
4.
INSTRUCTIONS.
5.
Depress door switch. Use a piece of tape to hold switch closed.
Make sure thermostat is calling for heat or jumper R and W/W1 thermostat ter-
6.
minals.
7.
Will furnace operate while flashing fault code?
8.
Replace furnace control board.
9.
Are personality plug wires making good connection?
The furnace will operate acceptably; however, a model selection circuit failure
has occurred and furnace control board is defaulting to last valid model selec-
10.
tion. Board replacement is recommended but not necessary. This fault code will
flash continuously.
11.
Fix poor terminal connection or replace personality connector.
Fault Code 22
SETUP ERROR—This fault indicates that setup switches SW-1 or SW-6 are ON when they should be OFF. The
following combinations will cause the fault:
• Thermostat call with SW-1 ON.
• Thermostat call with SW-6 ON.
• SW-1 and SW-6 both ON together.
STEP
1.
Turn power off and remove blower access panel.
Make sure thermostat is NOT calling for heating or cooling. Disconnect all ther-
2.
mostat terminal leads to make sure.
3.
Is setup switch SW-1 in ON position?
4.
Put setup switch SW-1 in OFF position.
Go to page number indicated in Index for CLEANUP AND START-UP
5.
INSTRUCTIONS.
6.
Is setup switch SW-6 in ON position?
7.
Put setup switch SW-6 in OFF position.
8.
Replace furnace control board.
17
YES
NO
GO TO
2
5
3
4
INDEX
6
7
9
8
4
10
11
4
4
YES
NO
GO TO
2
3
4
6
5
INDEX
7
8
5
5