Allen-Bradley controllogix 1756-L55M12 User Manual page 125

Hide thumbs Also See for controllogix 1756-L55M12:
Table of Contents

Advertisement

IMPORTANT
Worst-case Estimates of 1756-BA1 Battery Life
Controller
Temperature
1756-L55M12
60 °C (140 °F)
1756-L55M13
25 °C (77 °F)
0 °C (32 °F)
1756-L55M14
60 °C (140 °F)
25 °C (77 °F)
0 °C (32 °F)
1756-L55M16
60 °C (140 °F)
25 °C (77 °F)
0 °C (32 °F)
1756-L55M22
Use the values for the 1756-L55M13 controller.
1756-L55M23
1756-L55M24
Use the values for the 1756-L55M14 controller.
1756-L63
60 °C (140 °F)
25 °C (77 °F)
0 °C (32 °F)
Do not decrease the time after the BAT LED turns on.
If the BAT LED turns on when you apply power to the controller, the remaining
battery life may be less than this table indicates. Some of the battery life may
have been used up while the controller was off and unable to turn on the BAT
LED.
Time Before BAT LED Turns On
Power off 100%
Power off 50%
57 days
110 days
63 days
123 days
60 days
118 days
29 days
57 days
30 days
61 days
24 days
48 days
15 days
30 days
13 days
27 days
6 days
12 days
22 days
43 days
21 days
42 days
14 days
28 days
Maintain the Battery
Time after BAT LED turns on
and Power Is Cut Off
Yearly
decrease
23%
69 hours
17%
76 hours
17%
73 hours
23%
35 hours
17%
37 hours
17%
30 hours
23%
18 hours
17%
16 hours
36%
7 hours
23%
6 hours
17%
28 hours
17%
2.5 days
Publication 1756-UM001G-EN-P - January 2007