Caution for electrical work
You must install ELCB or MCCB + ELB
CAUTION
- ELCB: Earth leakage breaker
- MCCB: Molded case circuit breaker
- ELB: Earth leakage breaker
Do not operate the outdoor unit before completing the refrigerant pipe work.
Do not disconnect or change the cable inside the product. It may cause damage to the product.
Specification of the power cable is selected based on following installation condition; culvert installation/
ambient temperature 30 °C (86 °F)/ single multi conductor cables. If the condition is different from the ones
stated, please consult an electrical installation expert and re-select the power cable.
- If the length of power cable exceed 50 m (164.04 ft), re-select the power cable considering the voltage drop.
Use a power cable made out of incombustible material for the insulator (inner cover) and the sheath (outer
cover).
Do not use the power cable with the core wire exposed due to insulator damage occurred during removal of the
sheath. When the core wire is exposed, it may cause fire.
Exposed wire core
<The example of exposed core wire>
Insulator (inner cover)
Sheath (outer cover)
ENGLISH-59