Reference Section
Relay Output Wiring
Table 54 - 750-Series Control Board and I/O Module TB1 Relay Output Wiring
Relay Output
External Supply
76
R0NC
R0C
R0NO
Power
Source
753 Main Control Board
R1NO
R1C
R1NC
or
R0NO
R0C
R0NC
Power
Source
750-Series I/O Module
Rockwell Automation Publication 750-QS001A-EN-P - March 2015
Set Selection
Port 0: P230 [RO0 Sel] = Port 0: P935 [Drive Status 1], bit 7 = Faulted
View Results
Port 0: P225 [Dig Out Sts]
Set Selection
Port 4 (or port where your I/O module is installed): P10 [RO0 Sel] = Port 0: P935 [Drive Status 1],
bit 7= Faulted
View Results
Port 4 (or port where your I/O module is installed): P5 [Dig Out Sts]