Mitsubishi Electric MSZ-D30NA Service Manual page 62

Indoor unit
Hide thumbs Also See for MSZ-D30NA:
Table of Contents

Advertisement

Indication
No.
Symptom
LED1
LED2
(Red)
(Yellow)
20
Once
Lighting
21
Twice
Lighting
22
3 times
Lighting
Outdoor
unit oper-
ates.
23
4 times
Lighting
24
5 times
Lighting
25
9 times
Lighting
Outdoor
unit oper-
ates
26
Lighting
Lighting
Abnormal point / Condition
Primary current protection
The input current exceeds 15 A.
Secondary current protection
The current of the compressor exceeds 15 A.
High-pressure protection
The indoor gas pipe temperature exceeds 113°F (45°C) dur-
(MUZ)
ing heating.
The indoor gas pipe temperature falls 37°F (3°C) or below
Defrosting in cooling
during cooling.
Discharge temperature protec-
The discharge temperature exceeds 212°F (100°C) during
tion
operation.
The frequency of the compressor is kept 80 Hz or more and
Low discharge temperature
the discharge temperature is kept under 102°F (39°C) for
protection
more than 20 minutes.
Cooling high-pressure protec-
The outdoor heat exchanger temperature exceeds 136°F (58
tion
°C) during operation.
Inverter check mode
The unit is operated with emergency operation switch.
Normal
Condition
28
Remedy
These symptoms do not mean any abnormality of
the product, but check the following points.
Check if indoor fi lters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circulation is short
cycled.
Check refrigerant circuit and refrigerant amount.
Refer to 10-5.
"Check of LEV".
Refer to 10-5.
"Check of outdoor thermistors".
Refer to 10-5.
"Check of LEV".
Check refrigerant circuit and refrigerant amount.
This symptom does not mean any abnormality of
the product, but check the following points.
Check if indoor fi lters are clogged.
Check if refrigerant is short.
Check if indoor/outdoor unit air circulation is short
cycled.