Indication
No.
Symptom
LED1
LED2
(Red)
(Yellow)
20
Once
Lighting
21
Twice
Lighting
22
3 times
Lighting
Outdoor
unit oper-
ates.
23
4 times
Lighting
24
5 times
Lighting
25
9 times
Lighting
Outdoor
unit oper-
ates
26
Lighting
Lighting
Abnormal point / Condition
Primary current protection
The input current exceeds 15 A.
Secondary current protection
The current of the compressor exceeds 15 A.
High-pressure protection
The indoor gas pipe temperature exceeds 113°F (45°C) dur-
(MUZ)
ing heating.
The indoor gas pipe temperature falls 37°F (3°C) or below
Defrosting in cooling
during cooling.
Discharge temperature protec-
The discharge temperature exceeds 212°F (100°C) during
tion
operation.
The frequency of the compressor is kept 80 Hz or more and
Low discharge temperature
the discharge temperature is kept under 102°F (39°C) for
protection
more than 20 minutes.
Cooling high-pressure protec-
The outdoor heat exchanger temperature exceeds 136°F (58
tion
°C) during operation.
Inverter check mode
The unit is operated with emergency operation switch.
Normal
–
Condition
28
Remedy
•
These symptoms do not mean any abnormality of
the product, but check the following points.
•
Check if indoor fi lters are clogged.
•
Check if refrigerant is short.
•
Check if indoor/outdoor unit air circulation is short
cycled.
•
Check refrigerant circuit and refrigerant amount.
•
Refer to 10-5.
"Check of LEV".
•
Refer to 10-5.
"Check of outdoor thermistors".
•
Refer to 10-5.
"Check of LEV".
•
Check refrigerant circuit and refrigerant amount.
•
This symptom does not mean any abnormality of
the product, but check the following points.
•
Check if indoor fi lters are clogged.
•
Check if refrigerant is short.
•
Check if indoor/outdoor unit air circulation is short
cycled.
–
–