Viessmann VITODENS 100-W Installation And Service Instructions Manual page 37

Hide thumbs Also See for VITODENS 100-W:
Table of Contents

Advertisement

Fault messages on the display
Displayed
System characteris-
fault code
tics
b0
Burner blocked
b8
Burner blocked
E3
Burner in a fault
state
E5
Burner blocked
F0
Burner blocked
F1
Burner in a fault
state
F2
Burner in a fault
state
F3
Burner in a fault
state
(cont.)
Cause
Short circuit, flue
gas temperature
sensor
Lead break, flue
gas temperature
sensor
Fault in safety
chain.
Internal fault
Internal fault
Max. flue gas tem-
perature exceeded
Temperature limit-
er has responded
Flame signal is al-
ready present at
burner start
Troubleshooting
Measures
Check the sensor (see
page 44).
Check the sensor (see
page 44).
Check the temperature
limiter and connecting
leads (see page 42).
Check the control unit,
and replace if required.
Check the ionisation elec-
trode and connecting ca-
bles.
Initiate "Reset" (see
page 39).
Replace control unit.
Check heating system fill
level. Check circulation
pump. Vent the system.
Initiate "Reset" (see
page 39).
Check heating system fill
level. Check circulation
pump. Vent the system.
Check the temperature
limiter and connecting
leads (see page 42).
Initiate "Reset" (see
page 39).
Check ionisation elec-
trode and connecting ca-
ble.
Initiate "Reset" (see
page 39).
37