Window Master WSC 308 01 Operation Manual / Technical Information page 8

Smoke control unit

Advertisement

Technical data, Smoke central unit Type WSC 308 01
Connection possibilities:
1)
Motors up to 8A.
2)
Smoke detectors, differential heat detectors and/or maximum heat detectors, multi-sensor smoke
detectors (smoke/heat combination detectors), up to 15 units.
3)
Break glass units (primary), up to 6 units (max. current load of the alarm display = 250mA).
4)
Break glass units (secondary), up to 15.
Ventilation buttons with ‚open' indicator, up to 15, any number without ‚open' indicator (max.
5)
current load = 120mA).
6)
Wind/rain detectors with potential free N/O contact (max. current load of the detector = 250mA).
7)
ASC CLOSE function at the smoke detector input (insert ASV module).
Operating/control elements:
The reset button on the control PCB is used to reset a tripped smoke ventilation system and to close the
actuators.
Setting possibilities via slide switch SW1:
SW 1/1 = ON
Maintenance control is activated.
SW 1/1 = OFF
Maintenance control is not activated. Only a coded deactivation is possible following an
activation!
As a control of the activation, the operating LED flashes for 10 sec. If SW1/1 is switched back to OFF again
within this time, the activation process is deleted.
The maintenance control is triggered after the elapse of a 12 month time period. The yellow malfunction LED in
the break glass unit (primary) is lit, and a permanent acoustic alarm signal sounds. Also the green operating
LED is still lit to indicate the absence of a fault. A malfunction message has priority.
SW 1/2 = ON
The transmission of the alarm message (alarm malfunction module 1) is interrupted after 3
minutes.
SW 1/2 = OFF The alarm message (alarm malfunction module 1) is transmitted for as long as an alarm is
tripped.
Setting possibilities via slide switch SW2:
SW 2/1 = ON
The smoke control system trips following a malfunction message from the motor, smoke
detector, SHE switch circuit, over-temperature
SW 2/1 = OFF
The smoke control system does not trip following a malfunction message. The malfunction
message is only displayed by LED`s.
SW 2/2 = ON
The actuators only move OPEN for as long as the ventilation button is pressed (dead man
control).
SW 2/2 = OFF
The actuators move OPEN as soon as the ventilation button is pressed (self-hold).
MALFUNCTION REMEDY:
Diagnosis / monitoring in the smoke control unit:
LED's on the PCB's
Mains (green)
Operation (green)
Smoke detector (yellow))
Break glass unit (yellow)
Motor Circuit (yellow)
Battery/load control
(yellow)
Function OK
Malfunction
lit
lit
at any malfunction
off
flashes when interrupted,
is lit after a short circuit
off
flashes when interrupted,
is lit after a short circuit
off
flashes when interrupted,
after approx. 8 s
off
see diagnosis battery
Smoke control unit – Type: WSC 308 01
off
Check mains voltage and mains fuse
off
Check all functions Temp.
Check temperature fuse for 0 Ohm
Check wiring and the active end
Check wiring and jumper J1 in the
last or only break glass unit
Check motor end module and
Diagnosis
module
the motor fuse
see diagnosis battery
8