Commissioning WSC 308 01
When error message occur, please refer to chapter Operating elements/LED diagnosis.
An acoustic message only occurs in the break glass unit (primary) with the door closed or the door
contact switch pressed!
1) The smoke control unit is completely installed, without the operating voltage applied
a) Check all mechanical and electrical components for damage.
b) Check the DIP slide switches in the smoke control unit for their correct (required) position.
c) Check all screw and plug connections for tightness and/or firm seating.
d) Check that all external components are installed.
Actuators:
Automatic detectors:
Manual detectors:
2) With mains voltage, without battery
Adhere to the VDE regulations! Externally disconnect the mains voltage.
a) Connect the mains cables and reapply the mains voltage.
b) The mains LED is ON, the operating LED is OFF, the battery LED is ON. The malfunction signal at the
break glass units is ON.
3) With mains voltage, with battery
a) Remove the protection film from one face of the supplied foam rubber. Glue each foam rubber to the
bottom side of the batteries. Connect the batteries to the black battery bridge according to the wiring
diagram, then connect the red and the blue connection cable to the red and the black flat plug.
Remove the bottom protection film of the foam rubber and insert the batteries in the smoke control unit
according to figure 1 (symmetrically, with an approx. 3 mm spacing from the housing edge), and firmly
press down to the housing bottom!
b) Plug the red connection cable to the + and the blue connection to the flat plug of the smoke control
unit. Note: Check correct polarity!
c) The operating LED is ON, the battery LED is OFF. The malfunction signal at the break glass units is
OFF.
4) Ventilation button
a) Closely observe the actuators during opening and closing. They must not be impaired in any
position by the building structure. Also the motor connection cables must not be subject to
pulling or crushing.
b) Briefly actuate the Open button to have the actuators move open up to the final position. With the
SW2/2 =ON (hold-to-run) setting, the actuators only move as long as the button is pressed. The OPEN
display (if existing) in the button is ON.
c) Briefly actuate the CLOSED button, the actuators close. The Open display is OFF.
d) Press both buttons simultaneously while running, this corresponds to stop. The ventilation Open
display is ON, the actuators stop.
e) Briefly press the Close button again, the actuators fully close, the Open display is OFF.
5) Break glass unit
a) Open the door and press the red Open button. The actuators move open through to the end position.
The red alarm LED (also in the smoke control unit) is ON, at the same time a permanent acoustic
signal sounds (door contact pressed!).
b) While running, press the Close button at the ventilation button, then press both buttons, the actuators
must neither close nor stop!
c) Press the reset/Closed button in the break glass unit. The actuators close through to the end position.
The ventilation function is released again. The red alarm LED (also in the smoke control unit) and the
signal generator are OFF.
6) Break glass unit (secondary)
a) Check as described under 5). "Operation", "Malfunction" and the acoustic signal are missing!
Is the final module at the last or only actuator inserted?
Is the active end module at the last or only detector inserted?
Is the jumper only inserted in the last or only operating panel?
Smoke control unit – Type: WSC 308 01