Smoke control unit
Type:
WSC 308 01
Head office:
WindowMaster A/S
Skelstedet 13
2950 Vedbæk
Denmark
+45 45 67 03 00
www.WindowMaster.com

Advertisement

loading

Summary of Contents for Window Master WSC 308 01

  • Page 1: Table Of Contents

    Operation Manual / Technical information Smoke control unit Type: WSC 308 01 Table of contents: Safety information Operating elements / diagnosis LED's / fuse review Technical function description Technical data Installation and assembly Cable lengths table Cable plan Wiring diagram...
  • Page 2 The devices have been inspected and manufactured in accordance with the European directives. A corresponding manufacturer's declaration is available. You are only authorised to use the devices if a conformity declaration is issued for the entire system. Smoke control unit – Type: WSC 308 01...
  • Page 3: Operating Elements / Diagnosis Led's / Fuse Review

    Battery Autom. detector M800mA Motor 120mA T 8A PTC = overload protection, ist temperature rises to >80° C following a short circuit Mains T 1,6A External voltage 250mA Secondary transformer Primary transformer Smoke control unit – Type: WSC 308 01...
  • Page 4: Technical Function Description

    A malfunction in the cascaded smoke control units is detected via the 2 wire BUS cable. The malfunction is only displayed in the corresponding smoke control unit and in the break glass unit connected to the master smoke control unit. Smoke control unit – Type: WSC 308 01...
  • Page 5 Smoke control systems must be maintained by the builder at least once per year. The maintenance and check of the system must be documented in a test placard in the smoke control unit as well as in a logbook. Smoke control unit – Type: WSC 308 01...
  • Page 6 Display: The red alarm LED in the smoke control unit and the red LED in the break glass unit are lit. An alarm in the break glass unit (actuators “OPEN“ ) has priority over an ASV CLOSE signal. Smoke control unit – Type: WSC 308 01...
  • Page 7: Technical Data

    Technical data, Smoke central unit Type WSC 308 01 Supply voltage / mains connection 230V AC / 50Hz ( +10% / -15% ) Safety transformer according to EN 61558 Mains amperage 200VA Rated voltage (at 230V mains voltage) 24V DC , load dependent...
  • Page 8 Technical data, Smoke central unit Type WSC 308 01 Connection possibilities: Motors up to 8A. Smoke detectors, differential heat detectors and/or maximum heat detectors, multi-sensor smoke detectors (smoke/heat combination detectors), up to 15 units. Break glass units (primary), up to 6 units (max. current load of the alarm display = 250mA).
  • Page 9 Technical data, Smoke control unit Type WSC 308 01 Diagnosis / battery monitoring: Battery charge: Charging voltage 27.5V to 28V. Charging current limited to approx. 700mA. Short-circuit monitoring of the connection cables, charging voltage disconnected in the event of a short-circuit.
  • Page 10 Connect the connection cables in accordance with the terminal plan. Ensure that the connections are made correctly. Incorrect connection, number and colour errors could lead to malfunctions of the smoke control unit or of the external elements. Smoke control unit – Type: WSC 308 01...
  • Page 11: Cable Lengths Table

    Permissible cable length for the break glass unit supply cable when using..4x2x0.8mm: up to 200m The motor connection cable length to the junction box (or control module) must not exceed 10 m. Smoke control unit – Type: WSC 308 01...
  • Page 12: Cable Plan

    Cable plan Smoke control unit – Type: WSC 308 01...
  • Page 13 Standard wiring diagram Smoke control unit – Type: WSC 308 01...
  • Page 14 Various wiring diagrams Smoke control unit – Type: WSC 308 01...
  • Page 15 Various wiring diagrams Smoke control unit – Type: WSC 308 01...
  • Page 16 The ventilation function is released again. The red alarm LED (also in the smoke control unit) and the signal generator are OFF. 6) Break glass unit (secondary) a) Check as described under 5). “Operation”, “Malfunction” and the acoustic signal are missing! Smoke control unit – Type: WSC 308 01...
  • Page 17: Wiring Diagram

    If the start-up was unsuccessful (error with one of the test run processes), please refer to the chapter Function description and Operating elements / LED diagnosis. If necessary, check the wiring in accordance with the wiring diagram. Smoke control unit – Type: WSC 308 01...