Commissioning WSC 308 01
7) Automatic detectors
a) Spray test aerosol on the detectors.
b) The actuators move open through to the end position. The red LED in the detector, the red alarm LED
(also in the smoke control unit) and the permanent acoustic signal in the break glass unit are ON.
c) While running, press the Close button at the ventilation button, then press both buttons, the actuators
must neither close nor stop!
d) Press the reset/Close button in the break glass unit. The actuators close through to the end position.
The ventilation function is released again. The red alarm LED (also in the smoke control unit) and the
signal generator are OFF.
8) Emergency power supply test
a) Remove the mains fuse from the smoke control unit. Adhere to the VDE regulations!
b) The green mains and operating LED's are OFF, the yellow battery LED is flashing (smoke control unit
in the battery mode). The malfunction signal at the break glass units is ON.
c) The ventilation buttons are deactivated.
d) If the actuators were open, they will automatically close after 2 minutes.
e) Test the smoke trip and reset/close as described under 5).
f)
Refit the mains fuse.
g) The green mains and operating LED's are ON, the yellow battery LED is OFF. The malfunction signal
at the break glass units is OFF.
9) Activation of internal check
a) Move the DIP switch SW1/1 to ON
b) As a control of the activation the operating LED flashes for 10 sec.
c) If SW1/1 is switched back to OFF again within this time, the activation process is deleted.
d) After 10 sec. is the operating LED continuously lit, and the internal check is activated.
10) Wind/rain detector
a) Open the actuators with the ventilation button.
b) Wet the rain sensor, the actuators will fully close, the green wind/rain LED in the control centre is ON.
c) While running, press the Open button at the ventilation button, then press both buttons, the actuators
must neither open nor stop!
d) The SHE trip has priority.
When the start-up was successful, then close the doors of the break glass units and of the smoke control unit.
If the start-up was unsuccessful (error with one of the test run processes), please refer to the chapter Function
description and Operating elements / LED diagnosis. If necessary, check the wiring in accordance with the

wiring diagram.

Smoke control unit – Type: WSC 308 01
17