Download Print this page

Technical Data - Window Master WSC 308 01 Operation Manual / Technical Information

Smoke control unit

Advertisement

Technical data, Smoke central unit Type WSC 308 01
Supply voltage / mains connection
Safety transformer
Mains amperage
Rated voltage (at 230V mains voltage)
Emergency power supply batteries
Charging unit:
Charging voltage
Charging current
Operating duration (emergency power supply )
Current load of the actuators
Switch-on duration
Review of fuses
Type of connection to external
Cable monitoring
Message Alarm trip / malfunction
Environment class
Housing
Protection type according to DIN EN60529
Weight
Colour
230V AC / 50Hz ( +10% / -15% )
according to EN 61558
200VA
24V DC , load dependent
2x 12V / 7Ah 4 year operating time
27.5V 28V
700mA, current limited
72 hours if batteries are fully charged
8A max.
20%
Mains 1.6A slow-blow
Motor
8 A slow-blow
Battery
800mA medium slow-blow
Mains screw terminal / plug/screw terminals / 0.5-2.5sqmm
Motor screw terminal 0.5-10sqmm
automatic detectors (detector circuit with active end
module), break glass unit (detector circuit with end resistor,
actuators (with motor end module), batteries (cyclic
measurement)
optically alternating or steady signals by LED's
Operating and alarm tripping = steady signal. Malfunction
ofbattery, motor, break glass unit and smoke detector in the
event of an interruption = alternating, in the event of a short
circuit = steady signal
III according to VdS 2581 / 2593 (-5°C to +40°C)
Sheet steel housing, type KL-40/30-S103
surface-mounted
Protection class I
Dimensions WxHxD 400x300x120mm
IP 54
Central unit
RAL 7035
Smoke control unit – Type: WSC 308 01
without batteries approx. 8.8 kg
with batteries approx.
13.4kg