ABB i-bus KNX Product Manual page 36

Valve drive actuator vaa/s x.230.2.1
Hide thumbs Also See for i-bus KNX:
Table of Contents

Advertisement

ABB i-bus
KNX
Commissioning
Enable communication object
"Status control value" 1 byte/1 bit
Options:
The control status of the output is sent via this communication object.
1 bit: The communication object
appears:
34 2CDC 508 101 D0201 | VAA/S x.230.2.1
Control value on forced operation
in % [0...100]
Options:
0...30...100
This parameter determines the control value that the output should assume at forced operation.
If a control value is received via a 1 bit value, a value must be entered on parameter
PWM in s
[10...6,000], page 30. This value is used as the basis for calculation of the output control
at forced operation in %.
no
1 bit
1 byte
Send object value
Options:
no, update only
after a change
after request
after a change or request
no, update only: The status is updated but not sent.
after a change: The status is sent after a change.
after request: The status is sent after a request.
after a change or request: The status is sent after a change or a request.
Object value at control value > 0
Options:
1
0
If the communication object value is greater than 0, a telegram with the value 1 or 0 can be sent via
this parameter.
1 byte: The communication object
parameters are displayed:
value, page 45, (1 bit) and the following parameter
Status control
Status control
value, page 45, (1 byte) and the following
Cycle time of