Parameter Definition Of Fb7 P_Rcv_Rk - Siemens SIMATIC S7 CP340 Programming Manual

Table of Contents

Advertisement

4 ASCII protocol communication
4. Invoke Receive Function Block FB7 P_RCV_RK from Libraries -> CP PtP ->
CP341 and distribute instance data block DB7 to it. Set LADDR as the start
logic address 256 in hardware configuration.
5. Create receive data block DB10
Fig. 29: Receive data block DB10
6. Invoke receive function block
The parameters of the receive function block FB8 FB7 P_RCV_RK of CP341
are set as in the table below:
LADDR
DB_NO
DBB_NO
LEN
EN_R
R
NDR
ERROR
STATUS
Other
parameters
Table 6: Parameter definition of FB7 P_RCV_RK
CP340/CP341/CP440/CP441 Communication and Programming
Entry-ID: 88867653,
V1.0,
Start logic address in hardware configuration, which is
256 in this example
Send Data block number, which is 10(DB10) in this
example
Start address of Send Data, which is 0(DB10.DBB0) in
this example
Length of receive data, which is MW2 in this example.
This value is not 0 only in the current cycle when data are
received. The length of received data may be determined
by checking the MW4 value.
Enable receive bit, which is M0.1 in this example.
Cancel communication, which is not available in this
example
Receive complete bit, which is TRUE if Receive
completes and has no error
error bit, TRUE indicating that it has an error
status word, ID error code. See CP341 manual for related
descriptions
Irrelevant to ASCII communication protocol, and not
available in this example
02/2014
19