Install condensate drain trap as shown. Use ¾ " drain
connection size or larger. Do not operate without trap. Unit
must be level or slightly inclined toward drain.
All wiring should be made in accordance with the
National Electrical Code. The local Power Company
should be consulted to determine the availability of sufficient
power to operate the unit. The voltage, frequency, and phase
at the power supply should be checked to make sure it
corresponds
to
the
REQUIREMENT.
Install a branch circuit fused disconnect near the unit, in
accordance with the N.E.C. or local codes. Wire sizes and
overcurrent protection should be determined from the unit
nameplate ampacity and in accordance with Table 4 (page
6) or the N.E.C. Under no circumstances should wiring be
sized smaller than is recommended by either of these two
sources.
Fuses smaller than that recommended on the wiring diagrams
could result in unnecessary fuse failure or service calls.
The use of protective devices of larger size than indicated
could result in extensive damage to the equipment. The
manufacturer bears no responsibility for damage caused to
equipment as result of the use of larger than is recommended
size protective devices.
All units have undergone a run test prior to packaging for
shipment. This equipment has been started at minimum
rated voltage and checked for satisfactory operation. Do
not attempt to operate this unit if the voltage is not within
the minimum and maximum voltages shown on nameplate.
All exterior wiring must be within approved weatherproof
conduit. The unit must be permanently grounded in
accordance with local codes, or in absence of local codes,
with N.E.C ANSI/ NFPA NO. 70-1984 or latest edition by
using ground lug in the control box.
Fuses or HACR type circuit breakers may be used where
codes permit.
FOR INTERNAL WIRING SEE WIRING LABEL ATTACHED TO UNIT
L1
T1
T2
L2
CONTACTOR
T3
L3
HIGH VOLTAGE
DISCONNECT
HIGH VOLTAGE POWER WIRING
24 VOLT CONTROL WIRING
L3 CONNECTION - 3 PHASE ONLY
Note: Some single phase units are equipped with a single
pole contactor. Caution must be exercised when servicing
as only one leg of the power supply is broken with the
contractor.
To wire the unit, make the following high and low voltage
connections.

WIRING

unit's
RATED
VOLTAGE
LOW VOLTAGE CONNECTORS
Y G R W
SWITCH
R
G
FIGURE 6
HIGH VOLTAGE
D
ISCONNECT
M
THIS UNIT.
TO DO SO MAY CAUSE PROPERTY DAMAGE, PERSONAL INJURY O
DEATH.
High Voltage Wiring: (See Figure 6)
a.
Single Phase- Two leads should be connected to terminals
L1 & L2 in the electrical control section, using wire sizes
specified in wiring table.
b.
Three Phase- Three leads should be connected to terminals
L1, L2 and L3 in the electrical section, using wire sizes
specified in wiring table.
Low Voltage Wiring: (See Figure 6)
a.
Air Conditioners- Connect 24V wires from the thermostat to
the corresponding wires in the control box using No. 18AWG
as follows:
b.
Heat Pumps- Connect 24V wires from the thermostat to the
corresponding wires in the control box using No. 18AWG
as follows:
*Optional field installed heat connections

Internal Wiring:

A diagram detailing the internal wiring of this unit is located
on the electrical box cover. If any of the original wire supplied
with the appliance must be replaced, the wire gauge and
insulation must be the same as the original wiring.
Transformer is wired for 230 volts on the 208/230 models.
See wiring diagram for 208 volt wiring.
W
Y
BRANCH CIRCUIT AMPACITY 15 20 25 30 35 40 45 50
SUPPLY WIRE LENGTH -
6
WARNING
!
ALL
POWER BEFORE SERVICING OR INSTALLING
ULTIPLE POWER SOURCES MAY BE PRESENT. FAILU
LEAD
THERMOSTAT
Red
Green
Yellow
Y (Cool)
W hite
W 1 (Heat)*
Brown
W 2 (Heat)*
TABLE 2
TERMINAL
THERMOSTAT
Red
Green
Orange
O (Rev. Valve)
W hite
W 1 (Heat, 2nd)*
Brown
W 2 (Heat 3rd)*
Yellow
Y (Cool)
C (Blue)
C (Common)
TABLE 3
FEET
200
6
4
150
8
6
100
10
8
50
14 12 10 10
TABLE 4
RE
R
R (24V)
G (Fan)
R (24V)
G (Fan)
4
4
3
3
2
2
6
4
4
4
3
3
8
6
6
6
4
4
8
8
6
6