Customization Of Smss And Audible Reports - jablotron JA-60GSM Installation Manual

Dialer module
Hide thumbs Also See for JA-60GSM:
Table of Contents

Advertisement

Telephone number table
Entry
Memory
sequence
1
71 ______ F0
2
72 ______ F0
3
73 ______ F0
4
74 ______ F0
5
75 ______ F0
6
76 ______ F0
7
77 ______ F0
8
78 ______ F0
The default text and audible reports sent can be modified.
The dialer can report all possible events of the alarm system by SMS
(see table 4.1.1).
It is possible to set which events will be reported to which telephone
number.
There are factory default SMS texts available for all possible events and
for all possible event sources. All these texts can be edited.
It is possible to set which events should activate audible warnings.
The communicator can report all possible events by dialing programmed
numbers and playing an audible warning - if the call is answered
It is possible to change SMS command texts, which are used for remote
control of the system.
First enter the programming mode if you are going to use the following
programming sequences:
4.1 Events to be reported by SMS
Table 4.1.1 shows the complete list of all possible events in the alarm
system together with each corresponding index number. It also shows
which events are assigned to which telephone numbers to be reported
by SMS. You can make your own setting by using:
4.1.1
Table – SMS report assignments to telephone numbers
Event index
uu
01
Intruder alarm – instant zone
02
Intruder alarm – delayed zone
03
Fire alarm
04
Panic alarm
05
Wrong access code alarm
06
Alarm after power on
07
Tamper alarm
08
Tamper OK
09
Alarm end
10
Alarm canceled by a user
11
Arming
12
Disarming
13
Partial arming (Home)
14
No code arming
15
External communication failure
16
External communication recovery
17
Failure
18
Failure recovery
19
AC failure longer than 30 minutes
20
AC failure
21
AC recovery
22
Battery failure
23
Battery recovery
24
Enter programming mode
25
Exit programming mode
26
Remote access
27
Remote access – end
28
RF jamming
29
Internal communication failure
30
Internal communication recovery
31
Periodic test
The x marks in the table show which events are assigned to which telephone numbers for SMS reporting. If you modify these, we recommend you to
mark your settings in the table.
JA-60GSM dialer module
Reporting mode for the two corresponding phone numbers:
- ALARM SMS if there is any type of alarm in the system (intruder, fire, tamper, panic).
- Technical SMS about events in the system.
- ALARM SMS if there is any type of alarm
-
notifies the called person (if you answer such a call, you will hear an
ALARM CALL
audible warning).
- Technical SMS about events in the system.
- ALARM, ARMING & DISARMING SMS.
-
ALARM CALL
notifies the called person (if you answer such a call, you will hear an
audible warning).
- Technical SMS about events in the system.
-
notifies the called person (if you answer such a call, you will hear an
ALARM CALL
audible warning). This setting is suitable for notifying landline numbers.
Technical SMS about events in the system. This position is reserved only for the
service/installer organization.
4

Customization of SMSs and audible reports

Event
81 uu t y
where
uu
is the event index from 01 to 31 (see table 4.1.1)
t
is a telephone number memory location from 1 to 8
y
0 = reporting disabled, 1 = reporting enabled
Note: SMS reports consist of 4 text parts (installation name, event
name, event source name and time) – all of these texts can be edited
and customized, see section 4.2 for details. In a single SMS there can
be up to 160 characters using ASCI format, or 65 characters using
UNICODE format. Exceeding these limits will result in split messages.
The event " Internal communication failure" is generated if any of the
wireless detectors are lost under RF supervision.
The event "External communication failure" is generated if there is a
GSM signal outage longer than 15 minutes. The release of this event
is possible when GSM signal monitoring is set to ON.
Example: if you enter 810381 and a Fire alarm is triggered (event
index 03) by detector number 1, the following message will be sent to
th
the 8
telephone number: "Alarm system reports: Fire alarm Wireless
detector #1 Time: 16.04. 11:16"
1
2
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
- 5 -
Notes
Only numbers, which can accept
SMS, should be entered for the SMS
reports (mobile phones, provider's
call centers etc.)
Audible warnings can be sent both to
mobiles and to landlines too
The communicator can report all
possible events from the alarm
system, not only the events listed in
the table above. See section 4 for
details.
-
Telephone numbers
3
4
5
6
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
7
8
x
x
x
x
x
x
MFJ51212

Advertisement

Table of Contents
loading

Table of Contents