York 33p502-05 Installation Manual page 29

Lx ultra commercial geothermal/water source heat pumps single capacity
Table of Contents

Advertisement

Wiring Schematics cont.
Aurora Base Control 460/60/3 5-Speed ECM
T3
Note 4
T2
Red
Phase
Yellow
Guard
Monitor
T3
T2
(PGM)
CC
L1 L2 L3
L3
L2
Black (7)
White (8)
Red (9)
Blue
Blue
460V
460V
Note 5
Transformer
PGM
Y-OUT
Y
C
Yellow
Black/White (92)
Yellow (91)
Note 2
Isolation
Valve
2
1
3
Red
DH W Y2 Y1 G O/B C
(51)
Green
P2
(50)
ES
White
LS
(52)
ALM
K5
ALG
ACC COM
ACC NO
K6
ACC NC
LO
R
C
O/B
G
Y1
Y2
W
DH
P1
LED4
F1
RS485 NET
R
C
Accessory Relay
Operation
SW2-4 SW2-5
Cycle with Blower
On
On
Cycle with Compressor
Off
Off
Water Valve Slow Open
On
Off
Outdoor Air Damper
Off
On
Aurora Timing Events
Normal Mode
Event
Random Start Delay
5 to 80 seconds
Compressor On Delay
5 seconds
Compressor Minimum On Time
2 minutes
Compressor Short Cycle Delay
4 minutes
Blower Off Delay
30 seconds
Fault Recognition Delay – High Pressure
Less than 1 second
Start-Up Bypass – Low Pressure
2 minutes
Fault Recognition Delay – Low Pressure
30 seconds
2 minutes
Start-Up Bypass – Low Water/Air Coil Limit
Fault Recognition Delay – Low Water/Air Coil Limit
30 seconds
Fault Recognition Delay – Condensate Overflow
30 seconds
Thermostat Call Recognition Time
2 seconds
Auxiliary Heat Staging Delay
5 minutes
Emergency Heat Staging Delay
2 minutes
Water Valve Slow Open Delay
90 seconds
Reheat Delay
30 seconds
T1
Black
T1
L1
Green (93)
Black (95)
Yellow (96)
Red (97)
Black
Black
24V
Black/White
CC2
CC2
CC2
P9
P5
R LO
R
F FG CC CCG
HI
LO
G
K3
K4
K2
Aurora Base Control
(ABC)
LED5
G
G
RS485 NET
RS485 EXP
C
C
R
A- B+
N/A
R
A- B+
P8
P7
P6
Condensate
1 second on and 1 second off
Slow Flash
100 milliseconds on and 100 milliseconds off
Fast Flash
100 milliseconds on and 400 milliseconds off with a 2 second pause before repeating
Flash Code
Test Mode
Random Start Delay
1 second
Status LED (LED1, Green)
Fast Flash
< 1 second
Configuration LED (LED2, Yellow)
Fast Flash
5 seconds
Fault LED (LED3, Red)
Fast Flash
15 seconds
Status LED (LED1, Green)
2 seconds
Normal Mode
ON
No Software Overide
Less than 1 second
Control is Non-Functional
OFF
DIP Switch Overide
30 seconds
Test Mode
Slow Flash
ECM Configure Mode
30 seconds
Lockout Active
Fast Flash
Reset Configure Mode
30 seconds
Flash Code 2
Dehumidification Mode
30 seconds
Reserved
Flash Code 3
30 seconds
Reserved
Flash Code 4
2 seconds
Load Shed
Flash Code 5
20 seconds
ESD
Flash Code 6
7.5 seconds
Reserved
Flash Code 7
90 seconds
30 seconds
Unit Power Supply
Note 1
Ground
Neutral
Disconnect
L1
L1
L2
L2
L3
L3
Brown
Orange
Gray (30)
Black (35)
Resistor
RV
FD
LP
HP
P4
REV REV FP1 FP1 FP2 FP2 LPS LPS HPS HPS
K1
PWM
CFM
SW1
Status
G
C
P13
Fault
R
Off
FP1 – 15°F/30°F
FP2 – 15°F/30°F
RV – B/O
Acc – Dip 1
Acc – Dip 2
CC – Dual/Single
L – Pulse/Continuous
Reheat/Normal
SW2
Config
Y
CO
EH1
C
EH2
Y1
G
CC
C
P3
Brown (23)
Aurora LED Flash Codes
Configuration LED (LED2, Yellow)
Fault LED (LED3, Red)
Flash ECM Setting
Normal Mode
Slow Flash
Input Fault Lockout
Fast Flash
High Pressure Lockout
Off
Low Pressure Lockout
Low Air Coil Limit Lockout - FP2
Low Water Coil Limit Lockout - FP1
Reserved
Condensate Overflow Lockout
Over/Under Voltage Shutdown
Reserved
Reserved
Air/Water Coil Limit Sensor Error
29
LX ULTRA SERIES INSTALLATION MANUAL
460/60/3
G
Green
5-Speed ECM
Blower
Motor
5
4
3
2
1
Note 6
Tan (31)
Red (32)
Blue (33)
5-Speed ECM Low Voltage Connections
Model TAP-1 TAP-2 TAP-3 TAP-4 TAP-5
015
Blue
018
Blue
023
Blue
024
Blue
C
030
Blue
Black/White
036
Blue
R
Yellow
041
Blue
F
042
Blue
048
Blue
060
Blue
070
Blue
Notes:
1 - Optional, factory installed unit mounted disconnect.
On
2 - Optional, factory installed internal isolation valve.
1
2
3 - Optional, factory installed phase guard.
3
4
4 - Optional, factory installed phase guard. The yellow transformer wire shall
5
6
be connected directly to the CPU board, if this option is not installed.
7
8
5 - Refer to the 5-Speed ECM Low Voltage Connection Table.
6 - Wire is provided with the unit but not connected to the 5-Speed ECM.
Legend
Factory Low Voltage Wiring
Factory Line Voltage Wiring
Field Low Voltage Wiring
Field Line Voltage Wiring
Optional Block
DC Voltage PCB Traces
Field Zone Sensor Wiring
Internal Junction
Quick Connect Terminal
L1
Field Wiring Lug
Ground
Relay Contacts – N.O., N.C.
OFF
Capacitor
Flash Code 1
Flash Code 2
Fuse
Flash Code 3
Flash Code 4
CC – Compressor Contactor
Flash Code 5
CO – Condensate Overflow Sensor
Flash Code 6
ES – Emergency Shutdown
Flash Code 7
HP – High Pressure Switch
LP – Low Pressure Switch
Flash Code 8
FD – Freeze Detection Sensor
Flash Code 9
F1 – Fuse
Flash Code 10
Flash Code 11
C
Note 5
Red
Gray
Red
Gray
Red
Gray
Red
Gray
Red
Gray
Red
Gray
Red
Gray
Red
Gray
Red
Gray
Red
Gray
Red
Gray
Thermistor
T
Relay Coil
Switch - Condensate Overflow
Switch - High pressure
Switch - Low pressure
Polarized connector
G
Light Emitting Diode - Green
Y
Light Emitting Diode - Yellow
R
Light Emitting Diode - Red
SW1 – Push button
SW2 – DIP package 8 position
RB – Blower Relay
RV – Reversing Valve Coil
PGM – Phase Guard Monitor
RH – Reheat Valve Coil
97P819-07
3/8/12