Dry contact with economizer interface
Hide thumbs Also See for PQDSBC1:
Table of Contents

Advertisement

Compressor Stop Mode (B)

CONTROL_MODE_SW
Setting
B

Operating Mode Selection (C, D)

CONTROL_MODE_SW
Setting
C
D

Economizer Control Mode (E)

CONTROL_MODE_SW
Setting
E
Input A
Input B
Indoor unit operating (Compressor in stop mode), locked
OFF
OFF
Indoor unit prior operating condition maintained (Compressor not in stop mode),
ON
OFF
Indoor unit stopped, locked
OFF
ON
Indoor unit stopped, locked
ON
ON
Input A
Input B
Indoor unit stopped, unlocked
OFF
OFF
Indoor unit operating in cool mode / fan high, unlocked
ON
OFF
Indoor unit operating in heat mode / fan high, unlocked
OFF
ON
Indoor unit operating in fan high, unlocked
ON
ON
Indoor unit stopped, locked
OFF
OFF
Indoor unit operating in cool mode / fan high, locked
ON
OFF
Indoor unit operating in heat mode / fan high, locked
OFF
ON
Indoor unit operating in fan high, locked
ON
ON
Input A
Input B
Indoor unit prior operating condition maintained, unlocked
OFF
OFF
Indoor unit operating with thermal off in cooling mode, unlocked
ON
OFF
Indoor unit prior operating condition maintained, unlocked
OFF
ON
Indoor unit operating with thermal off in cooling mode, unlocked
ON
ON
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Operating Mode Description
unlocked
Operating Mode Description
Operating Mode Description
INSTALLATION
13

Advertisement

Table of Contents
loading

Table of Contents