Repairs
(cont.)
Check the temperature limiter
If the burner control unit cannot be reset after a fault shutdown, although the
boiler water temperature is below approx. 75 °C, check the temperature limiter.
1. Pull the leads from temperature lim-
iter A.
2. Check the continuity of the tem-
perature limiter with a multimeter.
3. Remove faulty temperature limiter.
4. Coat the replacement temperature
limiter with heat conducting paste
and install.
5. To reset press "Reset" key on the
control unit.
Troubleshooting
73