Troubleshooting
Fault finding
(cont.)
Display
System character-
fault code
istics
0b
Burner blocked
0C
Burner blocked
30
Burner blocked
38
Burner blocked
51
No DHW heating
59
No DHW heating
b1
Control mode
b5
Control mode
E4
Burner blocked
E5
Burner blocked
E6
Burner blocked
F0
Burner blocked
F2
Burner in fault state
68
Cause
Measures
Flow of water to
Check the circulation
low.
pump.
Air in heat ex-
Vent the heating sys-
changer.
tem.
Flow switch
Check the interconnect-
faulty.
ing cable.
Voltage to low.
Contact the electricity
supplier.
Boiler tempera-
Check the boiler tem-
ture sensor
perature sensor (see
shorted out
page 72).
Boiler tempera-
Check the boiler tem-
ture sensor lead
perature sensor (see
break
page 72).
Draw off tempera-
Check sensors (see
ture sensor short
page 74).
circuit
Draw off tempera-
Check sensors (see
ture sensor short
page 74).
circuit
Communication
Check connections and
fault
program-
replace the program-
ming unit (inter-
ming unit, if necessary.
nal)
Internal fault
Replace control unit.
Fault
supply
Replace control unit.
voltage
Internal fault
Check the ionisation
electrode and leads.
Press"Reset".
Water pressure
Top up water (see
too low
page 63).
Internal fault
Replace control unit.
Temperature limit-
Check the heating sys-
er has responded
tem water level. Check
the circulation pump.
Vent the heating sys-
tem. Check the tem-
perature limiter and
leads.
Press"Reset".