External termination via internal branche (e.g. sink
waste)
The condensate drainage pipe should have a minimum
outside diameter of 21.5 mm with no length restriction.
The connection should preferably be made downstream
of the sink waste trap. If the connection is only possible
upstream, then the air break is needed between the two
traps. This can be provided by the sink waste pipe
(
fig. 14 and fig. 15).
Buderus 500-24C/28C - Subject to modifications resulting from technical improvements
2
1
3
Fig. 15 External termination of condensate drainage
pipe via internal discharge branch (e.g. sink
waste) and condensate syphon
1.
Sink
2.
Boiler
3.
No length restriction
4.
Ø21.5 mm min.
5.
open end of pipe direct into gully, below ground but above
water level
2
4
3
Fig. 16 External termination of condensate drainage
pipe via internal discharge branch (e.g. sink
waste) and condensate syphon
1.
Sink
2.
Boiler
3.
No length restriction
4.
Ø21.5 mm min.
5.
open end of pipe direct into gully, below ground but above
water level
Installation
4
7215 3100-15.1TD
1
7215 3100-16.1TD
1
5
5
17