Liebert NXC
9.8 Efficiency, Heat Losses and Air Exchange
Item
Overall efficiency
100% load
Normal mode
66% load
(double-conversion)
33% load
ECO Mode
Battery mode
Heat losses & air exchange
Normal mode
Eco mode
No load
Maximum forced air cooling
(front intake, rear exhaust)
Note: 400Vac input and output, battery fully charged, full-rated linear load
User Manual 10H52188UM60 - Rev. 2 - 09/2012
Table 9-8 Efficiency, Heat Losses and Air Exchange
Unit
%
94.2
%
93.9
%
91.3
%
%
92.5
kW
0.55
kW
0.18
kW
L/sec
Rated power (kVA)
10
15
94.1
94.2
93.7
92.8
0.84
0.28
0.24
Product Specifications
20
94.0
94.5
93.9
98
93
1.15
0.37
208
63