Earth leakage current
The residual current detector (RCD) for the UPS upstream input power distribution should be:
 Sensitive to the DC unidirectional pulse (level A) in power distribution network
 Insensitive to the transient current pulse
The residual current circuit breaker (RCCB) must be sensitive to the DC unidirectional pulse (level A) in power distribution
network, but insensitive to the transient current pulse, as shown in Figure 3-3 respectively.
When using the earth RCD in split-bypass system or parallel system, the RCD should be installed at the upstream input power
distribution terminal to avoid generating false alarms.
The earth leakage current introduced by the RFI filter in the UPS ranges from 3.5mA to 1000mA. It is recommended to
confirm the sensitivity of each differential device of the upstream input power distribution and downstream power
distribution (to load).
User Manual 10H52188UM60 - Rev. 2 - 09/2012
Figure 3-2 External protective device for backfeed protection
Figure 3-3 RCCB symbols
Single UPS Installation And Commissioning
23