4.5.5 Setting up the Double Bus System parameters

Using the double bus system formed by 1 + 1 parallel system as an example, set 'System Configuration' to 'Parallel', 'Parallel
requisite units' to '1', 'Parallel Redundant Units' to '1'. For the master system, set 'LBS Function' to 'MASTER'. For the slave
system, set 'LBS Function' to 'SLAVE'. Ensure that the setting for '3 Phase Output or 1 Phase Output' of each single UPS in the
double bus system is same, as shown in Figure 4-8.