9.3.2.

Dry Operation

9.3.2.1.

Thermostat Control

[Intake Air Temp. - Remote Controller Setting Temp.] >
[Thermostat-OFF Temp. +0.5 °C]
Operated in corresponding frequency.
Frequency is decided after a completion of the starting
control (in 60 seconds).
When Room Temp. is below [Thermostat-OFF Temp.]
continuously for 3 minutes or more, it turns to Thermostat-
OFF operation.
When room temperature almost comes to Thermostat-OFF
Temp., the operation turns to the Minimum power & fan
speed: SSLo.
9.3.3.

Heating Operation

9.3.3.1.
Thermostat Control
[Intake Air Temp. - Remote Controller Setting Temp.] >
[Thermostat-OFF Temp. +0.5 °C]
Operated in corresponding frequency.
Frequency is decided after a completion of starting control
(in 60 seconds).
When Room Temp. is below Thermostat-OFF Temp.
continuously for 3 minutes or more, it turns to Thermostat-
OFF operation.
When room temperature almost comes to Thermostat-OFF
Temp., the operation turns to the Maximum power.
Dry
Power
Intake Air Temp.
Maximum
Difference (°C)
Rated
Intermediate
Minimum
(-2.50)
OFF
Heating
Power
Intake Air Temp.
OFF
Difference (°C)
Minimum
Intermediate
Rated
(+1.00)
Maximum
22
TE9DKE
TE12DKE
2.7kW
4.0kW
2.5kW
3.6kW
~
~
0.8kW
0.8kW
TE9DKE
TE12DKE
0.8kW
0.8kW
~
~
3.5kW
4.5kW
4.6kW
6.2kW