Electrical:
Models with 1500 W AC Platinum power supplies:
200 - 240 (nominal) V ac; 50 Hz or 60 Hz; 8.35 A
Input kilovolt-amperes (kVA) (approximately):
Models with 900 W AC Platinum power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 10.3 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 5.0 A
Input kilovolt-amperes (kVA) (approximately):
Models with 750 W Platinum AC power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 8.6 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 4.2 A
Input kilovolt-amperes (kVA) (approximately):
Models with 750 W Titanium AC power supplies:
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 4.2 A
Input kilovolt-amperes (kVA) (approximately):
Models with 550 W AC power supplies:
100 to 127 (nominal) V ac; 50 Hz or 60 Hz; 6.5 A
200 to 240 (nominal) V ac; 50 Hz or 60 Hz; 3.3 A
Input kilovolt-amperes (kVA) (approximately):
Models with -48Vdc 900 W power supplies:
-48 - -60 (nominal) V dc; 25.8 A
Input kilovolt-amperes (kVA) (approximately):
BTU output:
Minimum configuration: 461 Btu/hr (135 watts)
Maximum configuration: 6667 Btu/hr (1954 watts)
Noise level:
6.6 bels (operating)
6.4 bels (idle)

Warranty options

The System x3550 M5 has a three-year warranty with 24x7 standard call center support and 9x5 Next
Business Day onsite coverage. Also available are Lenovo Services warranty maintenance upgrades and
post-warranty maintenance agreements, with a well-defined scope of services, including service hours,
response time, term of service, and service agreement terms and conditions.
Lenovo warranty service upgrade offerings are country-specific. Not all warranty service upgrades are
available in every country. For more information about Lenovo warranty service upgrade offerings that are
available in your country, visit the Lenovo Services website:
https://www-304.ibm.com/sales/gss/download/spst/servicepac
System x3550 M5
Minimum configuration: 0.14 kVA
Maximum configuration: 1.967 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 1.194 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 1.015 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 0.965 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 0.732 kVA
Minimum configuration: 0.14 kVA
Maximum configuration: 1.237 kVA