Download Print this page
Carrier 58MTA Installation, Start-Up, And Operating Instructions Manual
Carrier 58MTA Installation, Start-Up, And Operating Instructions Manual

Carrier 58MTA Installation, Start-Up, And Operating Instructions Manual

Direct vent condensing gas furnace

Advertisement

HEATING
& COOLING
58MTA
Deluxe 4-Way
Multipoise
2-Stage
Direct Vent Condensing
Gas Furnace
Visit www.carrier.com
Installation, Start-up, and Operating Instructions
Sizes 060-120
NOTE:
Read
the entire
instruction
manual
before
starting
the
installation.
This symbol
+ indicates
a change
since
the last issue.
A93040
TABLE OF CONTENTS
SAFETY
CONSIDERATIONS
.....................................................
2
INTRODUCTION
..........................................................................
2
CODES
AND
STANDARDS
........................................................
3
Safety .........................................................................................
3
General
Installation
...................................................................
3
Combustion
and Ventilation
Air ..............................................
3
Duct Systems
............................................................................
3
Acoustical
Lining and Fibrous
Glass
Duct ..............................
3
Gas Piping
and Gas Pipe Pressure
Testing ..............................
3
Electrical
Connections
..............................................................
5
ELECTROSTATIC
DISCHARGE
(ESD)
PRECAUTIONS
........ 5
APPLICATIONS
............................................................................
6
General
......................................................................................
6
Upflow
Applications
.................................................................
6
Condensate
Trap Location
(Factury-Shipped
Orientation)
..........................................................................
6
Condensate
Trap Tubing
fEactory-Shipped
Orientation)
..........................................................................
6
Condensate
Trap Location
tAlternate
Upflow
Orientation/
..........................................................................
7
Condensate
Trap Tubing
(Alternate
Upflow
Orientation/.7
Condensate
Trap Field Drain Attachment
..........................
8
Pressure
Switch
Tubing .......................................................
g
Upper. Collector
Box and Inducer
Housing
(Unused)
Drain Connections
...............................................................
8
Condensate
Trap Freeze
Protection
....................................
8
Downflow
Applications
............................................................
8
Condensate
Trap Location ..................................................
8
Condensate
Trap Tubing .....................................................
8
Condensate
Trap
Field Drain Attachment
..........................
9
Pressure
Switch
Tubing .......................................................
9
Condensate
Trap Freeze
Protection
....................................
9
Horizontal
Left (Supply-Air
Discharge)
Applications
............ 9
Condensate
Trap Location
..................................................
9
Condensate
Trap Tubing
...................................................
10
Condensate
Trap Field
Drain
Attachments
......................
10
Pressure Switch
Tubing .....................................................
l0
Condensate
Trap Freeze
Protection
..................................
I1
Constrnct
a Working
Platform
..........................................
11
Horizontal
Right
(Supply-Air
Discharge)
Applications
........ 1I
Condensate
Trap Location
................................................
I 1
Condensate
Trap Tubing
...................................................
I 1
Condensate
Trap Field
Drain Attachment
........................
12
Pressure
Switch
Tubing .....................................................
12
Condensate
Trap Freeze
Protection
..................................
12
Construct
a Working
Platform
..........................................
12
LOCATION
..................................................................................
13
General
....................................................................................
13
Furnace
Location
Relative
to Cooling
Equipment
...............................................................................
13
Hazardous
Locations
...............................................................
14
INSTALLATION
.........................................................................
14
Leveling
Legs (If Desired)
.....................................................
14
Installation
in Upflow
and Downflow
Applications
............................................................................
14
Installation
in Horizontal
Applications
..................................
16
Air Ducts .................................................................................
16
General
Requirements
.......................................................
16
Ductwork
Acoustical
Treatment
.......................................
16
Supply
Air Connections
....................................................
16
Return
Air Connections
.....................................................
t6
Filter
Arrangement
..................................................................
17
Bottom
Closure
Panel .............................................................
18
Gas Piping ...............................................................................
18
Electrical
Connections
............................................................
19
115-V Wiring .....................................................................
19
24-V Wiring .......................................................................
2l
Accessories
........................................................................
21
Direct
Venting
.........................................................................
23
Remov,'d
of Existing
Furnaces
from Common
Vent
Systems
..............................................................................
23
Combustion-Air
and Vent
Piping .....................................
24
Concentric
Vent and Combustion-Air
Ternlination
Kit Installation
...................................................................
28
Multiventing
and Vent Terminations
................................
32
Condensate
Drain ....................................................................
32
General
...............................................................................
33
Application
.........................................................................
33
Condensation
Drain
Protection
.........................................
34
START-UP
ADJUSTMENT
AND SAFETY
CHECK
.............. 34
General
....................................................................................
34
Sequence
of Operation
............................................................
35
Two-Stage
Heating
With Single-Stage
Thermostat
(Adaptive
Model ................................................................
35
Manufacturer
reserves
the right to discontinue,
or change at any time, specifications
or designs
without notice and without incurring obligations.
PC 101
Catalog No. 535-80042
Printed in U.S.A.
Form
58MTA-3SI
Pg 1
7-02
Replaces:
58MTA-1SI