Remote Controller Wiring - Toshiba RAV-SM406BTP-E Original Instruction

Air conditioner (split type) indoor unit
Hide thumbs Also See for RAV-SM406BTP-E:
Table of Contents

Advertisement

 Wiring between indoor unit and outdoor unit
1. Figure below shows the wiring connections between the indoor and outdoor units and between the indoor units
and remote controller. The wires indicated by the broken lines or dot-and-dash lines are provided at the locally.
2. Refer to the both indoor and outdoor unit wiring diagrams.
3. The power of the indoor unit is supplied from the outdoor unit.
Wiring diagram
Single system
Remote controller

Remote controller wiring

A B
Indoor side
1
2
3
System interconnection
wires
Outdoor side
1
2
3
Power supply
Simultaneous triple and double twin system
Remote controller
Remote controller
inter-unit wiring
Remote controller
wiring
A B
Indoor side
Indoor side
1
2
3
System
interconnection wires
Indoor power
Outdoor side
1
2
3
inter-unit wiring
Power supply
* Use 2-core shield wire (MVVS 0.5 to 2.0 mm
and simultaneous double twin systems to prevent noise problems. Be sure to connect both ends of the shield
wire to earth leads.
* Connect earth wires for each indoor unit in the simultaneous twin, simultaneous triple and simultaneous double
twin systems.
27-EN
Simultaneous twin system
Remote controller
inter-unit wiring
Remote controller
Remote controller wiring
A B
Indoor side
Indoor
side
1
2
3
System interconnection wires
Indoor power
Outdoor side
1
2
3
inter-unit wiring
Power supply
Remote controller
Remote controller
inter-unit wiring
inter-unit wiring
A B
A B
Indoor side
Indoor side
1
2
3
1
2
3
Indoor power
Indoor power
inter-unit wiring
inter-unit wiring
Triple
Double twin
2
or more) for the remote controller wiring in the simultaneous triple
 Wire connection
REQUIREMENT
• Connect the wires matching the terminal numbers. Incorrect connection causes a trouble.
• Pass the wires through the bushing of wire connection holes of the indoor unit.
• Keep a margin (Approx. 100 mm) on a wire to hang down the electrical control box at servicing or other purpose.
• The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)
• Before performing wiring work in the electrical control box, remove the
air filter and the cover of the box (fixed with 2 screws).
• Remove screw A, and loosen screw B.
• Pull up and open the electrical control box cover.
• Tighten the screws of the terminal block firmly, and fix the wires with
A B
the cord clamps attached to the electrical control box. (Do not apply
tension to the connecting section of the terminal block.)
1
2
3
• Slide the electrical control box cover to install it. Do not pinch the wire
and make the gap as small as possible when installing the cover.
A B
1
2
3
10
50
Earth wire
 Remote controller wiring
Strip off approx. 9 mm the wire to be connected.
Wiring diagram
Terminal block for remote
controller wiring of indoor unit
A
B
Remote controller wire
(Locally procured)
– 14 –
Side D (Space: 8.5 mm)
Cord clamp
Remote controller
wiring
Select side C or D for the power cable clamping position referring to
the following table according to the cable type and diameter.
* Cable clamp can be attached on either right or left side.
When twin system are connected, clamp two cables with one cable
Earth screw
clamp.
Wire type
Cabtyre cable
4-core stranded wire 2.5 mm²
System interconnection
wire
Cabtyre cable
4-core stranded wire 1.5 mm²
1
2
3
10
30
System interconnection wire
System interconnection wire
Terminal block
Remote
A
controller
B
unit
Electrical control
box cover
Loosen screw B.
Remove screw A.
Side C (Space: 4 mm)
Specification
Cable clamping position
Side D
Side C
See the figure on the left for
system interconnection wires to
the terminal block.
EN
28-EN

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents