Laars pennant PNCH Installation And Operation Instructions Manual page 18

Low temperature
Table of Contents

Advertisement

Page 18
certified for outdoor installations, such installations
are not recommended in areas subject to freezing
temperatures, unless proper precautions are taken.
Power outage, interruption of gas supply, failure
of system components, activation of safety devices,
etc., may prevent a heater from firing. Any time a
heater is subjected to freezing conditions, and the
GPM Water Flow
Size
Soft
Normal
500
45
68
45
68
750
1000
45
68
1250
68
68
68
68
1500
1750
68
68
2000
112
112
Notes:
Soft Water = 1 to 7.5 grains hardness
Normal Water = 7.6 to 17 grains hardness
Figure 6. Suggested Piping — One Water Heater, One Tank.
Temperature Rise °F
Hard
Soft
Normal
90
19
13
90
28
19
90
38
25
90
31
31
90
38
38
90
44
44
112
30
30
Table 9. Temperature Rise — Water Heater.
heater is not able to fire, and/or the water is not
able to circulate, there is a risk of freezing in the
heater or in the pipes in the system. When water
freezes, it expands. This can result in bursting of pipes
in the system, or damage to the heater, which could
result in leaking or flooding conditions.
Contact the local factory representative or Laars
for additional information.
LPM Water Flow
Hard
Soft
Normal
9
170
257
14
170
257
19
170
257
24
257
257
28
257
257
33
257
257
30
424
424
Hard Water = more than 17 grains hardness
GPM = gallons per minute
LPM = liters per minute
LAARS Heating Systems
Temperature Rise °C
Hard
Soft
Normal
341
10
7
341
16
10
341
21
14
341
17
17
341
21
21
341
24
24
424
17
17
Hard
5
8
10
13
16
18
17