Nortec RH Series Installation Manual page 3

Blower pack

Advertisement

Remote Mounting of the Blower Pack with RH Series
1. This installation guide is intended to be used in conjunction with the RH Series installation
manual.
2. The remote mounted blower should be located at least 7' off the floor to prevent the discharged
steam from coming in contact with pedestrian traffic or any obstructions.
3. When installing the remote blower pack, ensure the primary voltage to the RH Series has been
switched off at the electrical panel, or that it is unplugged.
4. Find a suitable location for mounting the remote blower pack. The surface should be flat with
adequate clearances for the top, side, and front:
Table 1: Clearances of Remote Mounted Blower Pack with RH Series @ 100% Capacity
Operating Voltage
110-120V
208V
220-240V
0"
Figure 1: Blower Pack for RH Series – Clearances & Mounting
5. The blower pack has two teardrop (or keyhole) openings on the back of the cabinet for
mounting purposes. They are located 8 ¼" apart, and 1" from the top of the blower pack
cabinet.
6. Measure the screw locations and use two #8 screws, 2" long. The screws should be
anchored in a standard 2" x 4" wood stud or equivalent to ensure adequate support of the
blower pack and connecting steam hose.
Minimum Ceiling
Clearance
inches (cm)
8"
55"
62"
*Nominal conditions 70°F, 40% RH
Ceiling
(25.4mm)
Side
Frontal
Remote Mounting of the Blower Pack with RH Series
Minimum Side
Minimum Frontal
Clearance
inches (cm)
5"
15"
16"
1.5"
(38.1mm)
8.22"
(208.8mm)
1"
Wall Mounting
Holes
Clearance
inches (cm)
50"
73"
74"