Daikin BSV4Q100PV1 Installation Manual page 16

System air conditioners
Table of Contents

Advertisement

Transmission wiring from indoor unit
(to F1 and F2 terminals of indoor unit)
Clamp 2)-1 (Accessory)
Power supply wiring
(to P1 and S terminals
of terminal block)
Wiring through hole
NOTES
• Use ring-type crimp style terminal for connections to
the power terminal block. (Refer to Fig. 6)
Also, insulate the crimped area by attaching an insula-
tion sleeve, etc.
If these are not available, see the following section.
(a)Wiring of different thicknesses cannot be connected
to the power terminal block.
(A loose connection could cause abnormal heat-
ing.)
(b)When connecting wire of the same diameter, make
the connection as shown in the figure 7.
• Do not finish the conductive part of the power supply
wires with lead-tin solder.
• Use an appropriate screwdriver for tightening the ter-
minal screw.
Using a screwdriver that is too small could damage the
screw head and prevent proper tightening.
• Over tightening the terminal screw could damage the
screw.
Refer to the Table 4 for the terminal screw tightening torque.
• When fastening the wire, use the included clamp 2)-1 so as not to apply tensile force to the wire connection
and then securely fasten the wire. Also, after wiring is completed, organize the wiring so that the EL.
COMPO. BOX lid does not pop up and then properly replace the EL. COMPO. BOX lid.
Make sure no wires are pinched when replacing the EL. COMPO. BOX lid.
Always use the wire through hole to protect the wires.
• Do not pass the transmission wiring and power supply wiring through the same locations and outside of the
unit keep them separated by at least 50mm.
Not doing so could cause the transmission wiring to pick up electric noise (external noise) and result in a
malfunction or breakdown.
• After the wiring working is complete, use sealer (field supply) to seal closed the wire through hole.
(Entry by small animals, etc., could cause a malfunction.)
• As shown on the right-hand side, wrap the transmission wiring
between each BS unit and indoor unit with a finishing tape (field
supply) together with the on-site refrigerant piping.
14
Terminal block
Transmission wiring
Ground wire
from outdoor unit
Ground terminal
(to F1 and F2 terminals
of outdoor unit)
Wire
Wire fitting
Transmission wiring
from indoor unit
(to F1 and F2 terminals
Clamp 2)-1
of indoor unit)
(Accessory)
Transmission wiring from BS unit
Clamp 2)-1 (Accessory)
(to F1 and F2 terminals of BS unit)
Clamp 2)-1 (Accessory)
Clamp 2)-1 (Accessory)
Transmission wiring to
indoor unit (to F1 and F2
terminals on indoor side)
Ring-type crimp
style terminal
Connect wires of the
Do not connect
same gauge to both
wires of the same
sides.
gauge to one side.
Table 4
Terminal screw size
M3.5 (COOL/HEAT SELECTOR/transmission
wiring terminal block)
M4 (Power supply terminal block)
M4 (Ground terminal)
Transmission wiring
Liquid pipe
Liquid side pipe
Rear side
Insulation sleeve
Electric wire
Fig. 6
Do not connect
wires of different
gauges.
Fig. 7
Tightening torque (N/m)
0.80-0.96
1.18-1.44
1.52-1.86
Gas pipe
Insulation
Finishing tape