Toshiba MMU-AP0074YH-E(-TR) Service Manual page 134

Hide thumbs Also See for MMU-AP0074YH-E(-TR):
Table of Contents

Advertisement

N
. o
C
o
m
p
o
n
e
t n
6
Fan motor
Side cover
7
P
o r
c
e
1. Removing
1) Perform Step 1 of 1, Step 1 of 2, and Step 1 of 5.
2) Remove the clamp of the lead wire connected to
the following connectors of the control circuit
board.
NOTE
Unlock the housing part before removing the connector.
CN333: Fan motor power (5P: White)
CN334: Fan motor position detection (5P:
White)
3) Remove the screw of the metal fitting fixing the
fan motor. The earth screws are tightened
together. (Ø5 X 10, 2)
4) Hold and remove the fan motor in order not to
drop it.
2. Attaching
1) Fix the components again in the following order:
Fan motor
Motor fixing metal fittings
Electrical control box cover. Reconnect the
connector and earth lead removed in Step 1.
1. Removing
1) Perform Step 1 of 1.
2) Remove the screw of the side cover.
(One side: Ø4 X 12 With washer: 1)
3) Slide the side cover in the discharge direction to
remove it.
2. Attaching
1) Insert the hook of the side cover into the square
hole of the side of the main unit, and slide the
cover in the intake direction to attach it.
2) Insert the screw into the side cover.
(One side: Ø4 X 12 With washer: 1)
d
u
e r
– 134 –
R
e
m
a
k r
s
Fixing metal fittings
Screw
Sliding direction