Faber Relaxed L Installation Manual page 11

Table of Contents

Advertisement

Terminals located close to shared walkways, footpaths etc. could be subject to
legal constraints and this should be pointed out to the customer before installation.
If in any doubt about flue location advice should be sought from local building
control, or if appliance-related, from the manufacturer including wherever possible
a dimensioned sketch
Avoid locating the terminal in close proximity to plastic materials such as gutters or
other combustibles. If this is unavoidable then a suitable deflector should be made.
Some important requirements for a good functioning are
The wall-mounted terminal has to be at least 0,5 m off
o Corners of the building
o Below eaves
o Balcony's etc. unless the duct is dragged to the front side of the overhanging part
o The roof mounted terminal has to be at a distance of at least 0.5 meters of the
sides of the roof, excluded the ridge
3.2.2 Using an existing chimney as air inlet
You can connect the appliance onto an existing chimney. The existing chimney then
functions as air supply, where a flexible stainless steel liner (to BS715) of 100 mm performs
the flue function.
Requirements:
Any existing chimney used as an air supply must only service this a0ppliance.
A chimney that has previously been used for solid fuel must be swept before use.
The existing chimney needs to be airtight.
The existing chimney needs to have an opening of min. 150 x 150 mm.
The chimney needs to be intact and well looked after.
Use the adjustable roof-mounted-terminal especially made for this, and the
chimney connection set.
UK
IRL
>
>
>
> 10

Advertisement

Table of Contents
loading

Table of Contents