Heat Operation - Mitsubishi MSZ-FA-VA Service Technical Manual

Table of Contents

Advertisement

1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Room temperature minus set temperature : -1.0 : or more··············································ON
Room temperature minus set temperature : less than -1.0 :············································OFF
2. Indoor fan speed control
Indoor fan operates at the set speed by FAN SPEED CONTROL button.
When thermostat OFF (compressor OFF) fan speed becomes Very Low.
3. Coil frost prevention
Coil frost prevention is as same as COOL mode. (2-13.3.)
The indoor fan maintains the actual speed of the moment. However, when coil frost prevention works while the compressor
is not operating it's speed becomes the set speed.
4. Low outside temperature operation
Low outside temperature operation is as same as COOL mode. (2-13.4.)
2-15. HEAT (
) OPERATION
(1) Press OPERATE/STOP(ON/OFF) button.
OPERATION INDICATOR lamp of the indoor unit turns on with a beep tone.
(2) Select HEAT mode with OPERATION SELECT button.
(3) Press TEMPERATURE buttons (TOO WARM or TOO COOL button) to select the desired temperature.
The setting range is 16 ~ 31°C.
1. Thermostat control
Thermostat is ON or OFF by difference between room temperature and set temperature.
Room temperature minus set temperature : less than 2.0 :··············································ON
Room temperature minus set temperature : 2.0 : or more················································OFF
2. Indoor fan speed control
(1) Indoor fan operates at the set speed by FAN SPEED CONTROL button.
In Auto the fan speed is as follows.
Set temperature minus room temperature: 2 : or more·················································· High
Set temperature minus room temperature: Between 1 and 2 : ···································· Med.
Set temperature minus room temperature: less than 1 :················································· Low
(2) Cold air prevention control
1 When the compressor is not operating,
(1) if the temperature of room temperature thermistor RT11 is 15°C or less, or RT12 is less than 18°C,
the fan stops.
(2) if the temperature of room temperature thermistor RT11 is more than 15°C, or RT12 is more than 18°C,
the fan operates at Very Low.
2 When the compressor is operating,
(1) if the temperature of RT12 is 18°C or more, the fan operates at set speed.
(2) if the temperature of RT12 is less than 18°C and
(1) if heating operation starts after defrosting, the fan stops.
(2) if the temperature of room temperature thermistor RT11 is 15°C or less, the fan stops.
(3) if the temperature of room temperature thermistor RT11 is more than 15°C, the fan operates at Very Low.
NOTE : When 3 minutes have passed since the compressor started operation, this control is released regardless of the
temperature of RT11 and RT12.
Downloaded from AC-Manual.com Manuals
Initial temperature difference
Initial temperature difference
Initial temperature difference
38
Difference between room
temperature and set tem-
perature during operation
Thermostat
Set temperature
:
-1.0
-0.7
Difference between room
temperature and set tem-
perature during operation
Thermostat
Set temperature
1.7 : 2.0 :
Difference between room
temperature and set tem-
Fan speed
perature during operation
1 : 1.7 :
:
2 : 4 :