10-1 SETTING CEILING HEIGHT
• Set the SECOND CODE No. according to the ceiling height
as shown in the Table 4.
Table 4
Ceiling height (m)
Setting
FXFQ25 -
FXFQ100,
80SVM
Standard
2.7 or less 3.2 or less 13 (23)
High ceiling 1
2.7 - 3.0
High ceiling 2
3.0 - 3.5
10-2 SETTING AIR DISCHARGE DIRECTION
• Refer to the installation manual attached to the sealing
material of air discharge outlet sold separately and
engineering data book, for ceiling height settings for four-
direction (part of corner closed off) and three-direction.
(The SECOND CODE No. is factory set to "01" (all round
outlet) before shipping.)
10-3 SETTING WHEN AN OPTIONAL ACCESSORY IS
ATTACHED
• For setting when attaching an optional accessory, refer to the
installation manual attached to the optional accessory.
10-4 WHEN USING WIRELESS REMOTE CONTROLLER
• When using a wireless remote controller, it is necessary to
set the wireless remote controller address.
Refer to the installation manual attached to the wireless
remote controller.
10-5 SETTING FAN SPEED DURING THERMOSTAT
OFF
• Set the fan speed according to the using environment after
consultation with your customer.
• When the fan speed is changed, explain the set fan speed to
your customer.
Table 5
Setting
LL
Fan speed during
(Extra low)
cooling
thermostat OFF
Setting
LL
Fan speed during
(Extra low)
heating
thermostat OFF
Setting
10-6 SETTING FILTER SIGN
• A message to inform the air filter cleaning time will be
indicated on the remote controller.
• Set the SECOND CODE No. shown in the Table 6 according
to the amount of dust or pollution in the room.
• Though the indoor unit is equipped with the long life filter, it is
necessary to periodically clean the filter to avoid clogging of
the filter. Please also explain the set time to the customer.
• The periodical filter cleaning time can be shortened
depending on the environment.
3P335596-2D
English
FIRST
Mode
CODE
No.
No.
125SVM
0
5
0
3.2 – 3.6
13 (23)
5
0
3.6 – 4.2
13 (23)
5
FIRST
SECOND
Mode No.
CODE No.
CODE No.
12 (22)
6
12 (22)
3
Table 6
Contamination
Normal
SECOND
More
CODE
contaminated
No.
With indication
01
No indication*
01
* Use "No indication" setting when cleaning indication is not
02
necessary such as the case of periodical clean ing being carried out.
03
03
< TEST OPERATION >
03
• After cleaning the indoor unit inside, carry out test operation
according to installation manual attached to the outdoor unit.
• When the remote controller operation lamp flashes, it shows
that something is abnormal.
Check the malfunction codes on the remote controller.
The relation between the malfunction codes and malfunction details
is described in the operation manual attached to the outdoor unit.
Particularly, if the indication is one of those shown in the
Table 7, it may be an error in the electrical wiring or the
power supply is disconnected. Therefore, recheck wiring.
Table 7
Remote controller
indication
Though the central-
ized control is not
carried out, the lamp
"
" turns on.
"U4" turns on
"UH" turns on
No indication
01
02
• At test operation, if the decoration panel is mounted, check
01
the actuation of the swing blade.
02
CAUTION
After test operation is completed, check the items men-
tioned in the clause 2 "2. Items to be checked at deliv-
ery" on page 3.
If the interior finish work is not completed when the test
operation is finished, for protection of the air con d itioner,
ask the customer not operate the air conditioner until the
interior finish work is completed.
If the air conditioner is operated, the inside of the indoor
units may be polluted by substances generated from the
coating and adhesives used for the interior finish work
and cause water splash and leakage.
To the operator carrying out test operation
After test operation is completed, before delivering the air
conditioner to the customer, confirm that the control box
lid, the air filter and suction grille are attached.
In addition, explain the power supply status (power supply
ON/OFF) to the customer.
Hours until
FIRST
Mode No.
indication
CODE No.
Approx.
2500 hrs
Approx.
10 (20)
1250 hrs
Details
The terminals (T1 · T2) for FORCED OFF on
the indoor unit trans mission terminal block is
short circuited.
The power supply to the outdoor unit is not
made.
The power supply work to the outdoor unit is
not carried out.
The transmission wiring and the remote
controller wiring and FORCED OFF wiring
are connected wrongly.
The transmission wiring is disconnected.
The power supply to the indoor unit is not
made.
The power supply work to the indoor unit is
not carried out.
The remote controller wiring and the
transmission wiring and FORCED OFF
wiring are connected wrongly.
The remote controller wiring is disconnected.
SECOND
CODE No.
01
0
02
01
3
02
16