B. Mantel and Wall Projections
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specifi ed. Framing closer than the minimums list-
ed must be constructed entirely of noncombustible materials
(i.e., steel studs, concrete board, etc.)
Note: Measurement is taken from top of the
opening, NOT the top of the fi replace.
Combustible Mantels
All measurements are in inches.
12
11
10
9
8
7
6
5
4
3
9
1
8
7
6
5
4
3
TOP OF HOOD OR FIREPLACE OPENING
See Dimension V on Appliance
Dimension Diagram (Figure 3.1).
Figure 10.2 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
Non-Combustible Mantels
All measurements are in inches.
11
10
9
8
7
6
5
4
3
6
5
3/8
TOP OF HOOD OR FIREPLACE OPENING
See Dimension V on Appliance
Dimension Diagram (Figure 3.1).
Figure 10.3 Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles
54
Heat & Glo • SL-3X, SL-5X, SL-7X, SL-9X Installation Manual • 2372-980 Rev. C • 8/16
CEILING
32
13
12
11
10
CEILING
12
32
13
12
11
10
9
8
7
Combustible Mantel Legs or Wall Projections
TOP VIEW
MINIMUM
FIREPLACE OPENING
See Dimension B on Appliance
Dimension Diagram (Figure 3.1).
Note: Clearance from opening
to perpendicular wall.
Figure 10.4 Mantel Leg (Acceptable on both sides of opening)
Non-Combustible Mantel Legs or Wall Projections
TOP VIEW
FIREPLACE OPENING
See Dimension B on Appliance
Dimension Diagram (Figure 3.1).
Note: Clearance from opening
to perpendicular wall.
Figure 10.5 Wall Projection (Acceptable on one side of opening)
1/2 IN.
MINIMUM
2-7/8 IN.
3 FT. MAXIMUM
3 IN.
MINIMUM
5-7/8 IN.
MINIMUM
UNLIMITED