Viessmann VITODENS 200 Installation Instructions Manual page 6

Hide thumbs Also See for VITODENS 200:
Table of Contents

Advertisement

Preparing for installation
G Cable entry
Note
This boiler (protection level: IP X4 D)
is approved for installation in wet
rooms inside protection area 1
according to DIN VDE 0100, providing
the occurrence of hosed water can be
excluded.
Observe the requirements of DIN VDE
0100.
1. Prepare the water connections.
Flush the heating system thor-
oughly.
6
(cont.)
H Dimension with DHW cylinder
below.
K Condensate drain
2. Prepare the gas connection
according to TRGI or TRF or all
local regulations.
3. Prepare the electrical connections.
&
Power supply cable: NYM-
J 3 x 1.5 mm
230 V~, 50 Hz.
&
Accessory cables: NYM with the
required number of conductors
for the external connections.
&
Allow all cables in area "G" to
protrude 1200 mm from the wall.
2
, fuse max. 16 A,