5.12.2 Connections to the inputs and outputs

1
2
3
2-way
directional
valve
Terminals
Connection
1 to 3
2-way directional
valve
4 to 6
3-way directional
valve
Earth to 8
Electric immersion
heater
9 to 12
Room thermostat
13 to 14
Overload protec-
tion for hot water
tank
15 to 16
Temperature
sensor for hot
water tank
17 to 18
Ext. control signal
19 to 21
Solar 3-way direc-
tional valve
22 to 23
Solar pump station Input of the ON signal of Solar
Terminal strip and table of the input and outputs with function
Note
Note
Aquarea air / water heat pump – design handbook 07 / 2014
4
5
6
7
8
3-way
Electric
directional
immersion
valve
heater
Overload protection for hot water tank
Function
Output for the activation of the
2-way directional valves (e.g. for
underfloor heating system, cooling)
Output for the activation of the
3-way directional valves (e.g. for
heating, hot water tank)
Output for switching on / off the
electric immersion heater
Input for room thermostat signals
Input for overload protection
of the hot water tank
volt free
Input for temperature sensor
of the hot water tank
Input for external control signal
volt free
Output for activation of the solar
3-way directional valve
pump 2 (230 V AC)
For easy connection of a hot water tank provided by the customer,
Panasonic offers a temperature sensor installation kit for a foreign tank.
This article bears the designation CZ-TK1.
The outside temperature sensor is located in the outdoor or monobloc
unit and must not be installed or connected because the measured
values are transmitted via an internal BUS line.
9 10 11 12
13 14 15 16 17 18
Room
Temperature
thermostat
sensor for
hot water tank
5: Tank, 4: Heat
The maximum power of the hot water
electric immersion heater should be
maximum 3 kW
Terminals 13 / 14 must be bridged when
no overload protection is used for the hot
water storage
2 Kohlms @ 25 °C NTC
These two terminals are bridged during
delivery. Connection: 1-pole (min. 3 mm
contact gap)
Additional solar PCB required
Use additional circuit board CZ-NS1P,
CZ-NS2P or CZ-NS3P
Project Design
Electrical connection
Connections to the inputs and outputs
19 20 21
Solar 3-way
directional
valve
Ext. control signal
Condition
22 23
Solar pump
station
Cable
cross-
section
3 × min.
0.5 mm²
3 × min.
0.5 mm²
3 × min.
1.5 mm²
4 and / or
3 × min.
0.5 mm²
2 × min.
0.5 mm²
2 × min.
0.5 mm²
2 × min.
0.5 mm²
3 × min.
0.5 mm²
2 × min.
0.5 mm²