Project Design
Planning heat source – air

Fastening of the monobloc unit

Fastening of
the monobloc unit
Minimum requirements for
anchoring the Monobloc unit
to the floor or a foundation
(left) or directly to a base
plate (right)
Base
1
Gravel
2
3
Strip foundation
or base plate
Anchor bolt
4
5
Drainage pipe
All dimensions in mm
84
The monobloc unit must be mounted on one level, horizontal and on a
solid surface. Besides the weight of unit, also the weight of water must
be considered. Four anchoring bolts M12 are needed for fastening,
where the tightening force is minimum 15,000 N.
980
775
2
4
1
100
3
≥ 60
5
1
≥ 60 mm
4
≥ 300 mm
3
200
2
Aquarea air / water heat pump – design handbook 07 / 2014