Commissioning, inspection, maintenance
Further details regarding the individual steps
D

Inserting the turbulators

!
Please note
Burner adjustments and specific
system conditions can cause the
turbulators to move forward,
which may result in them being
burnt. This can also lead to dam-
age to the thermal insulation on
the boiler door.
Before insertion, the turbulators
must be slightly bent (see
steps).
A
10-15°
12
3. Remove combustion residues from
1. Push turbulators A approx. ¼ of
B
2. Bend turbulators approx. 10-15°.
3. Push the turbulators into the hot gas
(cont.)
the flue and the flue outlet through the
cleaning aperture in outlet D using a
vacuum cleaner.
their length into hot gas pipes B.
flues as far as they will go. When
doing this, check the prestress.
Note
Ensure that turbulators cannot easily
be pulled out of the hot gas flues.