Si01-406
1.9
Night Set Mode
This mode automatically keeps temperature slightly higher than the temperature setting. In this
way, there is no need to worry about overcooling while sleeping, and it also saves on electricity.
Notes:
No higher temperature setting on programme dry or auto operation.
1.10
Powerful Operation
During cool and dry operation, when the POWERFUL button on the remote controller is
pressed, the thermistor setting is changed to the lowest setting of the remote controller and the
fan runs at the maximum rpm (Note). During fan operation, air is blown at the maximum fan rpm.
Note ··· Max. fan rpm = H tap set by remote controller + 50 rpm
Notes:
1.11
3-minutes Standby Function
When the compressor turns OFF, it does not turn ON for 3 minutes.
Functions and Control
Set the OFF timer.
The unit will cool the room at the set temperature for 1 hour from when the timer starts
counting.
After that, the unit will raise temperature 0.5°C higher than the set temperature and cool for
30 minutes.
After that, the unit will raise temperature another 0.5°C and continue cooling at that
temperature.
It is possible to change the airflow setting while the OFF timer is in operation. However,
changing the airflow setting cancels the shift-up of the set temperature.
Timer start
Set temp.
60-minutes
In
COOL mode
To maximize the cooling effect, the temperature setting is fixed to 18°C and the air flow rate
is fixed to the maximum setting.
(H tap + 50 r.p.m)
The temperature and air flow settings are not variable.
In
DRY mode
The temperature setting is lowered by 3°C and the air flow rate is slightly increased. You can
repeat POWERFUL operation if you need even more dehumidification.
Functions of Cooling Only Models
0.5˚C
0.5˚C
30-minutes
(R1885)
27