Liquid Compression Protection Function 1; (Securing Of Differential Pressure And Blown Air Temperature) - Daikin FT25CV1A Service Manual

C-series
Hide thumbs Also See for FT25CV1A:
Table of Contents

Advertisement

Si01-406
3.8

Liquid Compression Protection Function 1

Differential Pressure and Blown Air Temperature)
Outline
To secure the reliability of the compressor (for dryness of suction refrigerant and differential
pressure) which is the primary purpose of the compressor, the lower limit of the output
frequency is limited to two stages under the condition of outside air temperature. This time, in
addition to this purpose, this function is adopted also for prevention of cold draught by securing
the blown air temperature at the time of heating operation by low-temperature out side air.
Processing
1. At the first step
2. At the second step
3. The set of a constant
DOA1CG, DOA2CG, DOA3CG, FCG7 and FCG8 have constants for Cooling / Heating
separately and these constants are distinguished with a suffix c/w.
4. Actual constant
Functions and Control
During operation of compressors.
Outdoor temperature ≤ DOA1CG
If
and
are under the simultaneous condition with AND, the lower limit of frequency in
this function is set at FCG7.
Compressors stop.
Outdoor temperature ≥ DOA2CG
If
and
are under the simultaneous condition with OR, the lower limit of frequency at the
first step control is cancelled.
During operation of compressors
Outdoor temperature ≤ DOA3CG
If
and
are under the simultaneous condition with AND, the lower limit of frequency in
this function is set at FCG8.
Compressors stop.
Outdoor temperature ≥ DOA4CG
If
and
are under the coordinate condition with OR, the lower limit of frequency at the
second step control is cancelled.
Outdoor temperature
DOA2CG
DOA1CG
DOA4CG
DOA3CG
The lower
Cancelled
frequency limit.
Cooling
DOA1CGC
18°C
DOA2CGC
20°C
DOA3CGC
14°C
DOA4CGC
16°C
FCG7C
34 Hz
FCG8C
34 Hz
DOA : Outdoor air temperature
CGC : Compressor guard for cooling
CGW : Compressor guard for heating
FCG : Frequency guard for compressor protection
Common setting for 25 / 35 class
FCG7
FCG8
Heating
DOA1CGW
0°C
DOA2CGW
2°C
DOA3CGW
–4°C
DOA4CGW
–2°C
FCG7W
34 Hz
FCG8W
34 Hz
Control for Heat Pump Models
(Securing of
FCG7
Cancelled
(R1044)