4-10. Input Power For 230 VAC

Y Always connect
grounding
conductor first.
= GND/PE

4-11. Electrical Service Guide For 230 VAC

Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Rating In Amperes
Min Input Conductor Size In AWG
Max Recommended Input Conductor Length In Feet (Meters)
Min Grounding Conductor Size In AWG
Reference: 1999 National Electrical Code (NEC)
1 Consult factory for circuit breaker applications.
2 "Time-Delay" fuses are UL class "RK5" .
3 "Normal Operating" (general purpose - no intentional delay) fuses are UL class "K5" (up to and including 60 amp), and UL class "H" ( 65 amp and
above).

4-12. Extension Cord Data

NOTE
Input Power
Phase
Input Voltage
115 V
1
230 V
1
2
L1
L2
1
2
Time-Delay
Normal Operating 3
When calculating max. cord length, remember to include conductor length from
line disconnect device to input power receptacle.
Hertz
60
60
1
L1
L2
230 VAC, 1
Conductor Size
10 AWG
12 AWG
See unit rating label for correct input
power (see Section 4-13).
1
Receptacle (NEMA 6-50R)
Customer Supplied
2
Line Disconnect Device
See Section 4-11.
Y Special installation may be
required where gasoline or
volatile liquids are present −
see NEC Article 511 or CEC
Section 20.
ssb2.2* 1/94 − Ref. 802 443-A
60 Hz Single Phase
230
25
30
35
12
79
(24)
12
Max. Cord Length
34 ft (10 m)
79 ft (24 m)
OM-1330 Page 15