Table of Contents HSU-18HEA03/R2(DB)-I Table of Contents 1. Introduction 1.1 Safety Cautions 2. List of Functions 4. Printed Circuit Board Connector Wiring Diagram 4.1 Indoor unit Connectors 4.2 Outdoor unit 5. Funcitions and Control 5.2 The control system of outdoor unit 5.3 Value of Thermistor...
Introduction HSU-18HEA03/R2(DB)-I 1. Introduction 1.1 Safety Cautions Be sure to read the following safety cautions before conducting repair work. The caution items are classified into “Warning” and “Caution”. The “Warning” items are especially important since they can lead to death or serious injury if they are not followed closely. The “Caution”...
Introduction HSU-18HEA03/R2(DB)-I Warning Do not repair the electrical components with wet hands. Working on the equipment with wet hands can cause an electrical shock. Do not clean the air conditioner by splashing water. Washing the unit with water can cause an electrical shock.
Page 5
Introduction HSU-18HEA03/R2(DB)-I Warning Be sure to use an exclusive power circuit for the equipment, and follow the technical standards related to the electrical equipment, the internal wiring regulations and the instruction manual for installation when conducting electrical work. Insufficient power circuit capacity and improper electrical work can cause an electrical the connections securely and route the cable properly so that there is no force pulling the cable at the connection terminals.
Introduction HSU-18HEA03/R2(DB)-I 1.1.3 Inspection after Repair Warning Check to make sure that the power cable plug is not dirty or loose, then insert the plug into a power outlet all the way. If the power cable and lead wires have scratches or deteriorated, be sure to replace them.
List of Functions HSU-18HEA03/R2(DB)-I 2. List of Functions Category Functions HSU-18HEA03/R2(DB)-I Healthy negative ion make your room full of an abundance natural negative ions. Child lock Avoid the child's wrong operation on the remote controller Use the timer function to set on,or off,or from on to off,or from off to...
Page 8
HSU-18HEA03/R2(DB)-I HSU-18HEA03/R2(DB)-I Model Cooling Heating 5.00(0.95~5.5) 5.22 Capacity Btu/h 18750 17070(3240~1870) Rated(Min.~Max.) kcal/h 4300 4489 Mositure Removal — Running Current(Read) 7.13 6.88 Power Consumption 1580(270-1950) 1600(350~2200) Read(Min.~Max.) Power Factor COP Rated (Min.~Max.) 3.16 3.26 Liquid Piping Connctions Drain Heat Insulation Both Liquid and Gas Pipes Max.
Page 9
HSU-18HEA03/R2(DB)-I Outdoor Unit HSU-18HEA03/R2(DB)-I Casing Color Ivory White Type Sroll Compressor Compressor Model 5CS130×CC03 Motor Output 1650 Model SRB68A Refrigerant Oil Charge 0.48 Model R410A Refrigerant Charge 1.00 /min 36.6 Air Flow Rate 1294 Type Propeller Motor Output Running Current (Rated) 6.88...
Connector Wring Diagram HSU-18HEA03/R2(DB)-I 4. Printed Circuit Board Connector Wiring Diagram 4.1 Indoor unit Connectors Connectors PCB(1) (Control PCB) 1) CN601 Connector for fan motor 2) CN9 Connector for STEP motor 3) CN8 Connector for heat exchanger thermistor and Room temperature thermistor...
Connector Wring Diagram HSU-18HEA03/R2(DB)-I Outdoor Unit Connectors PCB(1) (Control PCB) 1) CN1,CN2 Connector for power N and L 2) CN3 Connector for ground 3) CN6,CN7 Connector for terminal block 4) CN9,CN10 Connector for CN2,CN1 on the module board 5) CN11 Connector for four way valve coil...
Funcitions and Control HSU-18HEA03/R2(DB)-I 5. Funcitions and Control 5.1.1 automatic run mode When the running mode is turned to automation after starting the system, the system will first determine the running mode according to the current room temperature and then will run according to the determined mode.
Funcitions and Control HSU-18HEA03/R2(DB)-I for 10 minutes and then at the low dehumidify mode for six minutes. The indoor fan will operate at low speed. When Tr< Ts, the outsystem will be stopped, the indoor fan will be stopped for 3 minutes and then turned to the low speed option.
Page 16
Funcitions and Control HSU-18HEA03/R2(DB)-I Strength operation for 15 minutes. operation. When the system is at the automatic option with the strength/ mute function, if the system enters the cooling mode, the cooling strength/ mute function will be offered; if the system enters the heating mode, be no strength/ mute function.
Page 17
Funcitions and Control HSU-18HEA03/R2(DB)-I 5.1.9.2 Under the heating mode, after the setting of the dormant operation, the et temperature will fall 2 centigrades after 1 hour’s operation and will fall 2 centigrades 1 hours later. 3 hours after the preceding operations, the set temperature will be raised for 1 centigrade and the system will keep this status for 3 hours and then close down.
Page 18
Funcitions and Control HSU-18HEA03/R2(DB)-I be controlled by the thermostat. The outdoor system can be restarted when the coil temperature is below 42 and the system has been stopped for 3 minutes. The malfunction will be stored in the malfunction 5.1.13 Malfunction list resume Nothing is presented if there is no code list.
Funcitions and Control HSU-18HEA03/R2(DB)-I 5.2 The control system of outdoor unit 5.2.1.1 The operation frequency control of compressor Mode Heating 20Hz 100Hz Refrigeration 20Hz 90Hz 5.2.1.2 The starting of compressor 5.2.1.3 The speeds of increasing or decreasing the frequency of the compressor 5.2.1.4 The calculation of the compressor’s frequency...
Page 20
Funcitions and Control HSU-18HEA03/R2(DB)-I after 30 seconds,it begins to control the airflow speed according to the temperature conditions of the The temperature of the outdoor air (Ta) The temperature of the outdoor coil (Te) High Keeping the speed Medium Keeping the speed Stop 5.2.2.2 The outdoor fan control when heating...
Funcitions and Control HSU-18HEA03/R2(DB)-I If a single machine causes defrosting, the other machines all involve in defrosting. D. The conditions of withdrawing from defrosting The defrosting operation will change to heating operation, if any of the following conditions is (1) The temperature of the outdoor heat exchanger is continuously over 7°C for 80 seconds.
Page 22
Funcitions and Control HSU-18HEA03/R2(DB)-I he compressor stops Fgh_t1 2 gh_t1 6 5 Fgh_t2 59 Fgh_t 2 2 gh_t3 Fgh_t 3 2 gh_t4 Fgh_t4—2 I ncreasing slowly Fgh_t5 Fgh_t5—2 Normal Q:Continue to keep the last-time instruction cycle R:Increasing at the speed of 1Hz/10seconds Remarks: the outdoor unit 5.2.5.3 The control of preventing the overcurrent of the compressor...
Page 23
Funcitions and Control HSU-18HEA03/R2(DB)-I 5.2.5.5 Antifreezing protection of the indoor heat exchanger state). 11 //ice_temp_3+5 ce_temp_3+3 ncreasing slowly 8 //ice_temp_3+2 ice_temp_3 ice_temp_2 5 ecreasing slowly ice_temp_1 ecreasing rapidly i ce_temp_1 Stop thecompressor doesn’t change. underload malfunction, but don’t send malfunction report to the indoor.
Page 24
Funcitions and Control HSU-18HEA03/R2(DB)-I b) For the units’ malfunctins Annex 1 If there’s malfunction with the units, this will not affect the run of Remarks: in 3 minutes when the compressor stops, the units’ malfunctions are not displayed; the complete appliance’s malfunctions are prior to the units’ malfunctions.
Page 34
HSU-18HEA03/R2(DB)-I the nst ll on n test ope on of the on t n been mplet , t sho l be below. of the , to well, of s t.In to meet t s expe of the s s, s ff...
HSU-18HEA03/R2(DB)-I Introduction Cautions Safety Instructions and Warnings Disposal of the old air conditioner Before disposing an old air conditioner that Before starting the air conditioner, read the goes out of use, please make sure it's inop- information given in the User's Guide caref- erative and safe.
Page 36
HSU-18HEA03/R2(DB)-I Introduction Cautions 7. The appliance is not intended for use Do not obstruct or cover the ventilation by young children or infirm persons grille of the air conditoner.Do not put fingers without supervision. or any other things into the inlet/outlet and swing louver.
HSU-18HEA03/R2(DB) Introduction Cautions Safety Instruction Please read the following Safety Instructions carefully prior to use. The instructions are classified into two levels, WARNING and CAUTION according to the seriousness of possible risks and damages as follows. Compliance to the instructions are strictly required for safety use. Installation WARNING Please call Sales/Service Shop for the Installation.
Page 38
HSU-18HEA03/R2(DB) Introduction Cautions WARNING When abnormality such as burnt-small found, Use an exclusive power source with a immediately stop the operation button and circuit breaker contact sales shop. STRICT ENFORCEMENT Connect power supply cord Use the proper voltage Do not use power supply cord to the outlet completely extended or connected in halfway STRICT...
HSU-18HEA03/R2(DB) Introduction Parts and Functions Indoor unit Outlet Display board Inlet Air filter(inside) Air Purifying Filter (inside) Inlet grille Horizontal flap (adjust up and down air flow. Don't adjust it manually) Vertical blade Anion generator (adjust left and right air flow) (inside) Actual inlet grille may vary from the one shown in the manual according to the product purchased...
Page 40
HSU-18HEA03/R2(DB) Introduction Parts and Functions 10. TIMER ON display 11. FAN SPEED display AUTO 12. LOCK display 13. SWING UP/DOWN display 14. SLEEP display 15. HEALTH display 16. Operation mode display Operation mode AUTO COOL HEAT Remote controller Display board 17.Singal sending display 18.
HSU-18HEA03/R2(DB) Introduction Parts and Functions Clock Set When unit is started for the first time and after replacing batteries in remote controller, clock should be adjusted as follows: 1. Press CLOCK button,"AM" or "PM" flashes. POWER/SOFT 2. Press to set correct time. Each press will increase or decrease 1 min.
Page 42
HSU-18HEA03/R2(DB) Introduction Operation HEALTH operation Remote controller 1.Unit start Press ON/OFF on the remote controller, unit starts. 2.Health anion function Press HEALTH button. For each press, is displayed. Air conditioner starts health anion function operation. For twice press, disappears,the operation stops. When indoor fan motor is running, it has healthy process function.
Page 43
HSU-18HEA03/R2(DB)-I Introduction Operation uto Operation 1. Unit start Press ON/OFF on the remote controller, unit starts. Remote controller 2.Select operation mode Press MODE button. For each press, operation mode changes as follows: Remote controller: AUTO COOL HEAT Then Select Auto operation 3.Fan speed selection...
HSU-18HEA03/R2(DB)-I Introduction Operation Cool Operation 1. Unit start Press ON/OFF on the remote controller, unit sta rts. Remote controller 2.Select operation mode Press MODE button. For each press, operation mode changes as follows: Remote controller: AUTO COOL HEAT Then Select COOL operation 3.Select temp.setting...
HSU-18HEA03/R2(DB)-I Introduction Operation Dry Operation 1. Unit start Press ON/OFF on the remote controller, unit starts. Remote controller 2.Select operation mode Press MODE button. For each press, operation mode changes as follows: Remote controller: AUTO COOL HEAT Then Select DRY operation 3.Select temp.setting...
HSU-18HEA03/R2(DB)-I Introduction Operation Fan Operation 1. Unit start Remote controller Press ON/OFF on the remote controller, unit starts. 2.Select operation mode Press MODE button. For each press, operation mode changes as follows: Remote controller: AUTO COOL HEAT Then Select FAN operation 3.
HSU-18HEA03/R2(DB)-I Introduction Operation Heat Operation 1. Unit start Press ON/OFF on the remote controller, unit starts. Remote controller 2.Select operation mode Press MODE button. For each press, operation mode changes as follows: Remote controller: AUTO COOL HEAT Then Select HEAT operation 3.Select temp.setting...
Page 48
HSU-18HEA03/R2(DB)-I Introduction Operation Air Flow Direction Adjustment 1.Status display of air sending Horizontal louvers Pos.1 Pos.2 Pos.3 Pos.4 POWER/SOFT Pos.5 Pos.6 (Auto swing) 2.Up and down air flow direction For each press of button, air flow direction on remote controller displays...
HSU-18HEA03/R2(DB)-I Introduction Operation SLEEP operation starts SLEEP operation stops Sleep Operation Approx.6hrs Rises 1 1 hr Before going to bed, you can simply press the SLEEP button and unit will operate in SLEEP Rises 1 1 hr mode and bring you a sound sleep.
Page 50
HSU-18HEA03/R2(DB)-I Introduction Operation Timer On/Off Operation Set clock correctly before starting TIMER operation. 1. After unit starts, select your desired operation mode Remote Controller Operation mode will be displayed on LED. 2. Timer mode selection Press TIMER button to change TIMER mode. Every...
Page 51
HSU-18HEA03/R2(DB)-I Introduction Operation Timer On-Off Operation Set clock correctly before starting TIMER operation. 1. After unit starts, select your desired operation mode Operation mode will be displayed on LED. Remote Controller 2. Timer mode selection Press TIMER button to change TIMER mode. Every time...
Page 52
HSU-18HEA03/R2(DB)-I Introduction Operation POWER/SOFT Operation POWER Operation When you need rapid heating or cooling, you can use this funciton. Selecting of POWER operation Press POWER/SOFT button. Every time the button is pressed,display changes as follows: BLANK POWER SOFT Stop the display at...
Page 53
HSU-18HEA03/R2(DB)-I Introduction Operation Health airflow Operation 1.Press ON/OFF to starting The liquid crystal will display the working state of last time Remote controller (Except timer, sleeping, power/soft and health airflow). Setting the comfort work conditions. 2.The setting of health airflow function 1).Press the button of health airflow,...
HSU-18HEA03/R2(DB)-I Introduction Operation Emergency and Test Operation Emergency operation: Use this operation only when the remote controller is defective or lost. When the emergency operation switch is pressed,the" Pi "sound is heard once, which means the start of this operation.
Page 55
HSU-18HEA03/R2(DB)-I Introduction Maintenance For Smart Use of The Air Conditioner Setting of proper room Do not block the air inlet temperature or outlet Proper temperature Close doors and windows Use the timer effectively during operation During cooling operation, prevent the penetration of direct sunlight with curtain or blind.
Page 56
HSU-18HEA03/R2(DB)-I Introduction Maintenance Replacement of Air Purifying Filter 1.Open the lnlet Grille Prop up the inlet grille by using a small device named grille-support which located in the right side of the ind- oor unit. 2.Detach the standard air filter Slide the knob slightly upward to release the filter, then withdraw it.
HSU-18HEA03/R2(DB)-I Introduction Maintenance To Keep Your Air conditioner in Good Condition after Season. Operate in cooling mode for 2-3 hours. To prevent breeding mold or bad smell, be sure to operate at the designated temperature or 30 C,cooling mode and High speed fan mode for 2-3 hours.
HSU-18HEA03/R2(DB)-I Introduction Maintenance Before Setting in High season Cleaning the standard air filter. Operation without filter may cause troubles.Be sure to attach both right and left filters prior to the operation. Each of them are of different shapes. Connecting the earthing cable.
HSU-18HEA03/R2(DB)-I Introduction Trouble shooting Before asking for service, check the following first. Phenomenon Cause or check points The system does not restart When unit is stopped, it won't restart immediately. immediately until 3 minutes have elapsed to protect the system.
Service Diagnosis HSU-18HEA03/R2(DB)-I 7 Service Diagnosis 7.1 Caution for Diagnosis disabling equipment operation. 2.When a signal transmission error occurs the indoor and outdoor units. In either conduct Check Item None of the units Check to make sure that the rated voltage is supplied...
Service Diagnosis HSU-18HEA03/R2(DB)-I E1: Room temperature sensor failure E2: Heat-exchange sensor failure Detection Conditions Supposed Causes Correct the connection Is it normal? Thermistor resistance check Is it normal? Replace the thermistor Replace the indoor unit PCB Thermistor resistance check method: thermistor.
Page 62
Service Diagnosis HSU-18HEA03/R2(DB)-I Detection operation is used to determine abnormal fan motor operation Conditions Supposed Causes 1. Check connector connection. 3. Check motor control voltage (pins 4-3). 4. Check rotation command voltage output (pins 4-2). 5. Check rotation pulse input (pins 4-1).
Page 63
Service Diagnosis HSU-18HEA03/R2(DB)-I Turn o ff Does fan rotate Replace fan motor Turn o ff and d isconnect Does it rotate? fan motor connector turn Check outpue of fan motor connector Is motor v oltage DC310 gengerated ? Replace indoor unit PCB...
Page 64
Service Diagnosis HSU-18HEA03/R2(DB)-I Detection Conditions Supposed Causes Troubleshooting be occurred. If there is no response after might be broken FUSE of the indoor Replace the FUSE mainboard is broken The indoor PCB might be Domestic Air Conditioner...
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.4 IPM protection outdoor display LED1 flash 2 times: Method of IPM protection is detected by checking the compressor running condition and so on. Malfunction Detection Malfunction The system leads to IPM protection due to over current...
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.5 The communication fault between IPM and outdoor PCB outdoor display LED1 flash 4 times Method of Communication is detected by checking the IPM module and the outdoor PCB Malfunction Detection Malfunction The outdoor PCB broken leads to communication fault...
Page 67
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.6 Thermistor or Related Abnormality(outdoor unit) Frost-removing temperature sensor failure outdoor display: LED1 flash 10 times: Exhaust temperature sensor failure outdoor display: LED1 flash 13 times: Ambient temperature sensor failure outdoor display: LED1 flash 12 times: Method of This type of error is detected by checking the thermistor input voltage to the microcomputer.
Page 68
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.7 Overheat Protection For Exhaust Temperature outdoor display LED1 flash 8 times Method of the exhaust temperature control is checked with the temperature being detected Malfunction by the exhaust pipe thermistor Detection Malfunction when the compressor discharge temperature is above 117...
Page 69
HSU-18HEA03/R2(DB)-I Service Diagnosis The sensor is damaged. Replace the sensor Pull out the exhaust sensor and measure its with a new one. resistance standard temperatures according to the resistance-temperature table The sensor is damaged. Replace the sensor the results deviate with a new one.
Page 70
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.9 High work-intense protection Outdoor display LED1 flash 21 times Method of High work-intense control is activated in the heating mode if the temperature being sensed Malfunction by the heat exchanger thermistor exceeds the limit. Detection Malfunction...
Page 71
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.10 Power Supply Over or under voltagve fault outdoor display: LED1 flash 6 times The power supply is over voltage. Method of An abnormal voltage rise or fall is detected by checking the specified voltage detection circuit.
Page 72
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.11 Loop of the station detect error Outdoor Display LED1 flash 5 or 18 or 19 times Method of Malfunction the position of the compressor rotor can not detected normally Detection Malfunction when the The wiring of compressor is wrong or the connection is poor;...
Page 73
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.12 Over-current of the compressor Outdoor Display LED1 flash 3 or 24 or 25 times Method of Malfunction The current of the compressor is too high Detection Malfunction when the IPM Module is damaged Decision or the compressor is damaged Conditions power supply.
Page 74
HSU-18HEA03/R2(DB)-I Service Diagnosis 7.3.13 Communication error between the indoor and outdoor units Indoor Display Method of The date received from the another unit in indoor unit-outdoor unit signal transmission is Checked whether is normal Malfunction abnormal fan motor operation Detection...
Page 75
HSU-18HEA03/R2(DB)-I Service Diagnosis Check the status of LED1 on the indoor mainboard. If the LED1 blinks interruptedly measure voltage between Jumpers 3 and 4 of IC102 on the indoor mainboard with a multimeter. Test the outdoor power supply (230VAC and +310VDC) with a multimeter.
HSU-18HEA03/R2(DB)-I Installation 8 Installation Necessary Tools for Installation 1.Driver 5.Torque wrench(17mm,22mm,26mm) 9.Nipper 12.Reamer 2.Hacksaw 6.Pipe cutter 10.Gas leakage detector or 3.Hole core drill 7.Flaring tool soap-and-water solution 4.Spanner(17,19 and 26mm) 8.Knife 11.Measuring tape Drawing for the installation of indoor and outdoor units...
Page 77
HSU-18HEA03/R2(DB)-I Installation Floor fixing dimensions Floor fixing dimensions of the outdoor unit of the outdoor unit (Unit:mm) (Unit:mm) HSU-09HEA03/R2(DB)-I HSU-12HEA03/R2(DB)-I HSU-18 HEA03/R2(DB)-I Fix the unit to concrete or block with bolts( 10mm) and nuts firmly and horizontally. Fixing of outdoor unit When fitting the unit to wall surface, roof or rooftop, fix a supporter surely with nails or wires in consideration of earthquake and strong wind.
Page 78
HSU-18HEA03/R2(DB)-I Installation Indoor unit 1.Fitting of the Mounting Plate and Positioning of the wall Hole When the mounting plate is first fixed 1.Carry out, based on the neighboring pillars or lintels, a proper leveling for the plate to be fixed against the wall, then temporarily fasten the plate with one steel nail.
HSU-18HEA03/R2(DB)-I Installation Indoor unit 3.Installation of the Indoor Unit Drawing of pipe Rear piping Draw pipes and the drain hose, then fasten them with the adhesive tape Left Left-rear piping In case of left side piping, cut away, with a nipper, the lid for left piping.
Page 80
HSU-18HEA03/R2(DB)-I Installation Indoor unit 4.Connecting the indoor/outdoor Electric Cable Removing the wiring cover Remove terminal cover at right bottom corner of indoor unit, then take off wiring cover by removing its screws. When connecting the cable after installing the indoor unit 1.
HSU-18HEA03/R2(DB)-I Installation Outdoor unit 1.Installation of Outdoor Unit Drawing for the installation of indoor and outdoor units Install according to 2.Connection of pipes To bend a pipe, give the roundness as large as possible not to crush the pipe ,and the bending radius should be 30 to 40 mm or longer.
Page 82
HSU-18HEA03/R2(DB)-I Installation Outdoor unit 5.Purging Method:To use vacuum pump Liquid Side Gas Side 6.35mm(1/4") 9.52mm(3/8") 12.7mm(1/2") 3-way valve 2-way valve Detach the service port's cap of 3-way valve, the valve rod's cap for 2-way valve and 3-way's, connect Gaugemanifold(for R410A)
Page 83
HSU-18HEA03/R2(DB)-I Installation 1.Power Source Installation The power source must be exclusively used for air conditioner. (Over I0A) In the case of installing an air conditioner in a moist place, please install an earth leakage breaker. For installation in other places, use a circuit breaker as far as possible.
HSU-18HEA03/R2(DB)-I Removal Procedure 9. Removal Procedure 9.1 The removal procedure of Indoor Unit HSU18HEA03/R2(DB)-I 9.1.1 Removal of Front Panel Procedure Warning Be sure to wait 10 minutes or more after turning off all power supplies before disassembling work. Step Procedure Points 1.
Page 85
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points Pull the front panel out horizontally and remove it. Domestic Air Conditioner...
HSU-18HEA03/R2(DB)-I Removal Procedure 9.1.2 Removal of Air Filter Step Procedure Points Insert the air upwards slightly and then pull it when installing. out downwards. When installing, insert 2 hooks of the Domestic Air Conditioner...
Page 87
HSU-18HEA03/R2(DB)-I Removal Procedure 9.1.3 Removal of the blade Step Procedure Points Release the Insert the air marked hooks. Pull out and when installing. remove the blade. When installing, insert 2 hooks of the Domestic Air Conditioner...
Page 88
HSU-18HEA03/R2(DB)-I Removal Procedure 9.1.4 Removal of Front Case Step Procedure Points Release the screw covers Loosen the 2 Domestic Air Conditioner...
Page 89
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points Loosen the marked hooks. Pull out the front case. Domestic Air Conditioner...
Page 90
HSU-18HEA03/R2(DB)-I Removal Procedure 9.1.5 Removal of Vertical Blades and Display Board Step Procedure Points Pull out the Vertical Blades. screws,and remove the display board. Loosen the screw of the drip proof plate. Lift and remove the electrical box. Domestic Air Conditioner...
Page 91
HSU-18HEA03/R2(DB)-I Removal Procedure 9.1.6 Removal of Fan Drain pan and Electrical Box Step Procedure Points Loosen the 2 screws. Pull out the drain pan. Discharge the static electricity Loosen the screw of from your body the drip proof plate. before touching the...
Page 92
HSU-18HEA03/R2(DB)-I Removal Procedure 9.1.7 Removal of Fan Motor and Heat Exchanger Step Procedure Points 1. Remove the right side plate. Loosen the 2 screws. Remove the Lift up the evaporator Be careful not to evaporator. 3. Remove the fan. Loosen the 2 screws.
Page 93
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points Lift up the right part of the fan motor and slide it to the rightward to remove. Lift up the right part of the fan and remove it Domestic Air Conditioner...
HSU-18HEA03/R2(DB)-I Removal Procedure 9.2 The removal procedure of Outdoor Unit HSU-18HEA03/R2(DB)-I 9.2.1 Removal of Outdoor panel Step Procedure Points 1. Features Loosen the service Be careful not to cover screw and remove the service cover. exchanger. Domestic Air Conditioner...
Page 95
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points 2. Remove the panels. Loosen the 4 screws and lift the top panel Loosen the screws of the panel. Pull and remove the front panel. Domestic Air Conditioner...
Page 96
HSU-18HEA03/R2(DB)-I Removal Procedure 9.2.2 Romoval of Electrcal Box Step Procedure Points screws, then lift the electrical box Domestic Air Conditioner...
Page 97
HSU-18HEA03/R2(DB)-I Removal Procedure 9.2.3 Romoval of the Side panel Step Procedure Points screws and remove the side panel. Domestic Air Conditioner...
Page 98
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points Remove the back panel. screws and remove the side panel. 9.2.3 Romoval of Fan and Fan Motor Domestic Air Conditioner...
Page 99
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points Put the lead wire Loosen the throughthe back of motor when remove the fan assembling. (so as not to entangled with the propeller fan) Domestic Air Conditioner...
Page 100
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points screws and lift the fan motor. Domestic Air Conditioner...
Page 101
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points screws, then lift the fan motor bracket Domestic Air Conditioner...
Page 102
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points screws, then lift the proof plate. Domestic Air Conditioner...
Page 103
HSU-18HEA03/R2(DB)-I Removal Procedure 9.2.5 Romoval of compressor and heat exchanger Step Procedure Points Cut down the conecting pipe and pull out the compressor and remove the value bracket. Domestic Air Conditioner...
Page 104
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points Loosen the marked Domestic Air Conditioner...
Page 105
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points hook and remove the heat exchanger Domestic Air Conditioner...
Page 106
HSU-18HEA03/R2(DB)-I Removal Procedure Step Procedure Points Remove the valve bracket. Domestic Air Conditioner...
Page 111
Appendix HSU-18HEA03/R2(DB)-I Outdoor Unit control board Circuit Diagrams CN10 AC -L OUT AC -N OUT AC-N OUT AC -L OUT CN14 CN13 COM COM L FUSE1 PTC1 2U/450V T25A 250VAC 470N AC -L 100/1W S14K350 225/275V 225/275V 225/275V 8MH/20A 8MH/20A...
H-heat pump Nominal cooling capacity (18000BTU/h) The structure code of indoor & outdoor unit: S(wall-mounted) H-Abbreviation of Haier Examples: HSU-07RD03/R1,It represents wall-mounted split type heat pump air conditioner .The cooling capacity is 7000BTU/h,and the power supply is 220-230V/50Hz,”D” means the developing sequence,and"R1"...