Installation Guidelines

• Where a wall or other obstacle is in the path of outdoor unit's intake or exhaust airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.
Wall facing one side
More than 50
More than 100
1200
or less
Side view

Precautions on Installation

• Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare four sets of M8 or M10
foundation bolts, nuts and washers each which are available on the market.)
• It is best to screw in the foundation bolts until their length are 20mm from the foundation surface.

Outdoor Unit Installation

1.

Installing outdoor unit.

1) When installing the outdoor unit, refer to "Precautions for Selecting the Location" and the "Outdoor Unit Installation
Drawings".
2) If drain work is necessary, follow the procedures below.
2.
Drain work (heat pump-models).
1) Use
drain plug for drainage.
B
2) If the drain port is covered by a mounting base or floor surface, place
additional foot bases of at least 30mm in height under the outdoor unit's feet.
3) In cold areas, do not use a drain hose with the outdoor unit.
(Otherwise, drain water may freeze, impairing heating performance.)
3.
Flaring the pipe end.
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing
downward so that the chips do not enter the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
WARNING
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
■English
Walls facing two sides
More than 150
More
than 100
More than 50
Top view
(Cut exactly at
right angles.)
Set exactly at the position shown below.
Walls facing three sides
More than 50
More than 50
Bottom frame
B
Hose (available commercially,
inner dia. 16mm)
Flare's inner
surface must
be flaw-free.
Remove burrs
Flaring
A
Flare tool for R410A
Clutch-type
Clutch-type (Rigid-type)
A
0-0.5mm
1.0-1.5mm
Die
More than 150
More than 300
Top view
Unit: mm
Drain-water hole
Drain plug
Check
The pipe end must
be evenly flared in
a perfect circle.
Make sure that the
flare nut is fitted.
Conventional flare tool
Wing-nut type (Imperial-type)
1.5-2.0mm
4