Application Information
5) Additional Charge
The refrigerant charge has already charged into the outdoor unit. For the piping length of 7.6m, additional
refrigerant charge after vacuuming is not necessary.
When the piping length is more than 7.6m, please use the table below (unit in gram).
Cooling Only
Indoor
Outdoor
Add. Charge, g/m
Indoor
Outdoor
Add. Charge, g/m
Indoor
Outdoor
Add. Charge, g/m
Heatpump
Indoor
Outdoor
Add. Charge, g/m
Indoor
Outdoor
Add. Charge, g/m
Indoor
Outdoor
Add. Charge, g/m
Example: FHC25EXV1 & R25CXV1 with 13m piping length, additional piping length is 5.5m. Thus,
Additional Charge = 5.5m x 38g/m
= 209g