Advanced Programming - Withings WS-50 Quick Installation Manual

Table of Contents

Advertisement

Advanced programming

Parameter Name
Default Value
Detector Parameters
Walk Test LED
Off
Time Out
20 minutes
(Time adjustment)
Manual Time Out
10 minutes
Sensitivity On
9
Sensitivity Off
9
Lux time
0
Power Up State
On
On Delay
0 minutes
Inhibit
4 seconds
Factory default
-
Switching functions
To set Channel 1 functions - go to "Ch1(sw) Set " menu on the handset
To set Channel 2 functions - go to "Ch2(dim) Set " menu on the handset
Detection Mode
Presence
Lux on level
9
(Switch level on)
Lux off level
9
(Switch level off)
User Modes
Override On
-
Override Off
-
Cancel
-
6
Range / Options
Description
On or Off
When set to On this causes a red LED to flash on the sensor when it detects
movement. Use this feature to check for adequate sensitivity levels.
0-99 minutes
Once the detector is turned on, this value sets how long the lights will stay on once
movement has ceased. Select 0 for 10 second delay – use for commissioning only.
0-99 minutes
When a manual operation occurs, either via the switch input or the infrared, it
invokes the timeout period.
Example 1: a detector in presence mode has a detector timeout of 15 minutes and
a manual timeout of 3 minutes. When the user leaves the room they press the off
button. The sensor will revert to automatic after 3 minutes, and then walking back
in the room will turn the lights on.
Example 2: using the settings above, the user turns the lights off (say for a
presentation) but stays in the room. Every time a movement is detected, the
manual timeout period is re-triggered, but when it doesn't pick up for the short
timeout period, the sensor will timeout and revert to automatic. This means the
lights may turn on inadvertently during the presentation, if the occupants are still
for the manual timeout period, so adjust the timing carefully.
Sensitivity level for detecting movement when the detector is already on. *UHS5
1 (min) to 9 (max)
sets Sensitivity On and Off to the same value.
1 (min) to 9 (max)
Sensitivity level for detecting movement when the detector is off. *UHS5 sets
Sensitivity On and Off to the same value.
0 (disabled)
If the detector measures the lux level and decides that the output needs switching
on or off as a consequence, the lux time must elapse first. If at any time during the
1-99 minutes
timed delay the lux change reverses then the process is cancelled. Lux Time
enables absence detection to be implemented with a lux off level set. When the
button is pressed, the lights will go on, regardless of ambient light level. However,
if there is sufficient ambient light, they will turn off again after the Lux Time. Note
that whenever the an external switch is pressed, whether in absence or presence
mode, if the lights were out because of the lux level, they will be immediately
turned on again for at least the Lux Time.
Select No for a 30 second delay on start up. If Yes is selected, there will be no
On or Off
delay on start up and the detector will always power up detecting.
0-99 minutes
The On Delay to allows the first channel to switch on after the second channel. A
typical application for this would be where a detector is controlling lighting and air
conditioning in an area. When the occupant is detected, the lighting will be turned
on immediately, whereas the air conditioning may be turned on after 15 minutes. If
the area is vacated and the detector times out before the delay, then the air
conditioning would never go on. The delay can be set only for channel 1 using the
on delay parameter.
When the detector turns off, a delay is instigated to prevent retriggering. In certain
1 to 999 seconds
circumstances this delay may not be enough. This parameter allows the delay to
be changed.
-
Restores factory default settings
Presence or
Presence mode allows the output to turn on when movement is detected and off
when movement ceases. Absence mode allows the output to turn off when
Absence
movement ceases, but must be manually turned on first.
1 to 9
Sets a minimum light level below which the PIR sensor is enabled, allowing lights
to be turned on by movement.
For a higher
Note: the Lux Level Off value must always be greater than the Lux Level On value.
resolution a scale
of 101-199 is
available
1 to 9
Sets a maximum light level above which the PIR sensor is disabled, preventing
lights from being turned on by movement.
For a higher
resolution a scale
of 101-199 is
available
If the lights are off, sending the IR command will turn them on immediately and
-
revert to automatic operation using the manual timeout period .
-
If the lights are on, sending the IR command will turn them off immediately. After
the manual timeout period (described above), the sensor will revert to automatic.
Cancels the on or off override, returning the detector to normal operation.
-
UHS5 UNLCDHS
*
*

Advertisement

Table of Contents
loading

Table of Contents