CONFIGURING THE NS1
The following steps describe how to configure the NS1.
1. Wake up the NS1 from sleep mode.
When powering up the NS1 for the first time, the NS1 is in the Installer sleep mode.
This programmer will automatically become the Installer Remote Programmer. It is
recommended to identify the Remote Programmer as the Installer by labelling it such.
Figure 3 indicates how to wake up the NS1.
1. Power on. (NS1 is in
Installer Sleep mode.)
Figure 3
Waking up the NS1
2. Set the Lock Type (23*).
Different lock types can be set by entering the key sequence corresponding with the lock type.
See the following table for information.
Lock Type
Normally open
Normally closed
Coded signal
The default value is 23*0*. To set another value, take the steps indicated in Figure 4.
1. Enter Program mode by
presenting Installer Remote
Programmer.
Figure 4
Setting Lock Type
4 - 8
2. Present a Remote
Programmer in the RF
field of the NS1.
Key sequence
Description
23*0*
The settings "normally open" and "normally closed" are used when a lock
is directly connected to the NS1.
23*1*
Coded signal is used to trigger an external relay on the Connection Unit
23*2*
(article NS1CU). The external relay offers a higher level of security.
2. Enter the choice for the Lock Type, where
"n" is 1 or 2.
3. Normal operation of the
NS1 is resumed.
3. Normal operation of the
NS1 is resumed.
TD1166 rev1003