Indoor Unit Drain Piping - Panasonic CS-ME9PB4EA Service Manual

Hide thumbs Also See for CS-ME9PB4EA:
Table of Contents

Advertisement

11.5 INDOOR UNIT DRAIN PIPING

During drain piping connection, be careful not to exert extra force on the drain port at the indoor unit.
The outside diameter of the drain connection at the indoor unit is 32mm.
Piping material: Polyvinyl chloride pipe VP-25 and pipe fittings.
Be sure to perform heat insulation on the drain piping.
Heat insulation material: Polyethylene foam with thickness more than 8 mm (local supply).
Drain piping must have down-slope (1/50 to 1/100); be sure not to provide up-and-down slope to prevent reversal
flow.
Be sure to check no air trap on drain hose and to ensure smooth water flow and no abnormal sound.
The height of drain may be possible up to 750 mm.
Drain Test
The air conditioner uses a drain up motor to drain water. Use the following procedure to test the drain up motor operation.
Connect the main drain pipe to exterior and leave it provisionally until the test comes to an end.
Feed water to the flexible drain hose and check the piping for leakage.
Be sure to check the drain up motor for normal operating and noise when electric wiring is complete.
When the test is complete, connect the flexible drain hose to the drain port.
Pour about 600-700cc of water in the drain pan of the indoor unit. (Pour from the position specified in the drawing
by using a water supply bottle or other suitable tool.)
Press the drain pump test run on PCB to start the drain motor, and verity water drainage.
(The drain motor will automatically stop after operating for about five minutes.)
When drain set piping, install as shown in the
figure below.
38

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cs-me12pb4eaCs-me18pb4eaCs-me21pb4ea

Table of Contents