Daikin RXH20CVMB Technical Data Manual page 6

Table of Contents

Advertisement

2
Specifications
1
2
ELECTRICAL DATA
RXH20CVMB
Indoor unit
FTXS20CVMB
RXH25CVMB
Indoor unit
FTXS25CVMB
RXH35CVMB
Indoor unit
FTXS35CVMB
SYMBOLS
MCA
: Min. Circuit Amps (A)
MFA
: Max. Fuse Amps (A)
RHz
: Rated operating frequency(Hz)
RLA
: Rated Load Amps (A)
OFM
: Outdoor Fan Motor
IFM
: Indoor Fan Motor
FLA
: Full Load Amps
W
: Rated motor output (W)
4
• Pair Application, Inverter Controlled Unit • R-410A • RXH20-25-35CVMB
Outdoor unit
Hz-Volts
RXH20CVMB
50-230
Outdoor unit
Hz-Volts
RXH25CVMB
50-230
Outdoor unit
Hz-Volts
RXH35CVMB
50-230
• Split - Sky Air • Outdoor Units
Power supply
Voltage range
MCA
MFA
MAX. 50Hz 253V
14.0
15
MIN. 50Hz 207V
Power supply
Voltage range
MCA
MFA
MAX. 50Hz 253V
14.0
15
MIN. 50Hz 207V
Power supply
Voltage range
MCA
MFA
MAX. 50Hz 253V
14.0
15
MIN. 50Hz 207V
NOTES
1. RLA is based on the following conditions:
Indoor temp.: 27°CDB/19.0°CWB
Outdoor temp. : 35°CDB
2. Maximum allowable voltage unbalance between phases is 2%
3. Select wire size based on the larger value of MCA.
4. Instead of fuse, use circuit breaker.
5. For more details concerning conditional connections, see
http://www.daikineurope.com/extranet, select ''Daikin
Documentation'' and select ''conditional connection'', ''the
requested product type'' and ''English'' from the drop down
lists, click the search button.
Finally, click on the document title of your choice.
Compressor
OFM
RHz
RLA
W
FLA
42
2.81
25
0.35
Compressor
OFM
RHz
RLA
W
FLA
47
3.21
25
0.35
Compressor
OFM
RHz
RLA
W
FLA
70
4.41
25
0.35
IFM
W
FLA
18
0.20
3D044323
IFM
W
FLA
18
0.20
3D044324
IFM
W
FLA
18
0.20
3D044325